IPE300 series engineering VFD
Function parameter list
-131-
Function
code
Name
Description
Default Modify
P04.01
Torque boost of
motor 1
In order to compensate for low-frequency torque
characteristics, you can make some boost
compensation for the output voltage.
relative to the max. output voltage V
b
.
defines the percentage of cut-off
frequency of manual torque boost to the rated
motor frequency f
b
. Torque boost can improve the
low-frequency torque characteristics of V/F.
You need to select torque boost based on the
load. For example, larger load requires larger
torque boost, however, if the torque boost is too
large, the motor will run at over-excitation, which
may cause increased output current and motor
overheating, thus decreasing the efficiency.
When torque boost is set to 0.0%, the VFD uses
automatic torque boost.
Torque boost cut-off threshold: Below this
frequency threshold, torque boost is valid;
exceeding this threshold will invalidate torque
boost.
Output voltage
Output
frequency
Cut-off
boost
b
f
f
v
v
setting
range:
0.0%:
Automatic,
0.1%
–10.0%
setting range: 0.0%
–50.0%
0.0%
○
P04.02
Torque boost
cut-off of motor 1
20.0%
○
P04.03
V/F frequency
point 1 of motor 1
When
=1 (multi-dot V/F curve), you can
set the V/F curve through
The V/F curve is generally set according to the
load characteristics of the motor.
Note:
V1 < V2 < V3, f1 < f2 < f3. Too high voltage
for low frequency will cause motor overheat or
damage and cause VFD overcurrent stall or
overcurrent protection.
0.00Hz
○
P04.04
V/F voltage point
1 of motor 1
00.0%
○
P04.05
V/F frequency
point 2 of motor 1
0.00Hz
○
P04.06
V/F voltage point
2 of motor 1
0.0%
○