IPE300 series engineering VFD
Function parameter list
-118-
Functio
n code
Name
Description
Default Modify
output frequency)
setting range: 0.00
–30.00s
setting range: 0.0
–100.0%
setting range: 0.0
–50.0s
P01.13
FWD/REV running
deadzone time
This function code indicates the transition time
specified in
switching. See the following figure:
Output frequency f
Forward
Reverse
Deadzone
time
Time t
Starting
frequency
Switch over after
zero frequency
Switch over after
starting frequency
Setting range: 0.0
–3600.0s
0.0s
○
P01.14
FWD/REV running
switching mode
0: Switch at zero frequency
1: Switch at the starting frequency
2: Switch after the speed reaches the stop speed
with a delay
0
◎
P01.15
Stop speed
0.00
–100.00Hz
0.50Hz
◎
P01.16
Stop speed
detection mode
0: Detect by the set speed (unique in space
voltage vector control mode)
1: Detect by the feedback speed
0
◎
P01.17
Stop speed
detection time
0.00
–100.00s
0.50s
◎
P01.18
Terminal-based
running command
protection at
power-on
When the channel of running commands is
terminal control, the system detects the state of
the running terminal during power-on.
0: The terminal running command is invalid at
power-on. Even the running command is
considered as valid during power-on, the VFD
does not run and it keeps the protection state
until the running command is canceled and
enabled again.
1: The terminal running command is valid at
power-on. If the running command is considered
as valid during power-on, the VFD is started
automatically after the initialization.
0
○