IPE300 series engineering VFD
Basic operation guidelines
-94-
Function
code
Name
Description
Default
44: C_RO1 from PLC (Set P27.00 to 1.)
45: C_RO2 from PLC (Set P27.00 to 1.)
46: C_RO3 from PLC (Set P27.00 to 1.)
47: C_RO4 from PLC (Set P27.00 to 1.)
48: Auxiliary motor 1 startup
49: Auxiliary motor 2 startup
50: Remote brake (DP communication)
51: PT100 pre-alarm
52: PT1000 pre-alarm
53: OFF1 main contactor actuation
54: S terminal input 1 is valid
55: S terminal input 2 is valid
56: Brake release command action
57
–63: Reserved
Output terminal polarity
selection
0x00
–0x0F
0x00
Y switch-on delay
0.000
–50.000s
0.000s
Y switch-off delay
0.000
–50.000s
0.000s
HDO switch-on delay
0.000
–50.000s (valid when
0.000s
HDO switch-off delay
0.000
–50.000s (valid when
0.000s
RO1 switch-on delay
0.000
–50.000s
0.000s
RO1 switch-off delay
0.000
–50.000s
0.000s
RO2 switch-on delay
0.000
–50.000s
0.000s
RO2 switch-off delay
0.000
–50.000s
0.000s
Output terminal status at
present fault
0
Digital output terminal
status
0
5.5.13 Simple PLC
Simple PLC is a multi-step speed generator, and the VFD can change the running frequency and
direction automatically based on the running time to fulfill process requirements. Previously, such
function was realized with external PLC, while now, the VFD itself can achieve this function.
The VFD can realize 16-step speeds control, and provide four groups of acceleration/deceleration
time for choose.
After the set PLC completes one cycle (or one step), one ON signal can be output by the multifunction
relay.