IPE300 series engineering VFD
Basic operation guidelines
-52-
acceleration/deceleration time of voltage and frequency respectively, which form a real-time V/F curve
in combination manner.
Note:
This type of V/F curve separation can be applied in various variable-frequency power sources.
However, exercise caution when setting parameters as improper settings may cause equipment
damage.
Function
code
Name
Description
Default
Speed control mode
0: Sensorless vector control (SVC) mode 0
1: Sensorless vector control (SVC) mode 1
2: Space voltage vector control mode
3: Closed-loop vector control mode
Note:
If 0, 1 or 3 is selected, it is required to carry
out motor parameter autotuning first.
2
Max. output
frequency
–400.00Hz
50.00Hz
frequency
50.00Hz
Lower limit of running
frequency
0.00Hz
0.00Hz
ACC time 1
0.0
–3600.0s
Model
depended
DEC time 1
0.0
–3600.0s
Model
depended
Type of motor 1
0: Asynchronous motor (AM)
1: Synchronous motor (SM)
0
Rated frequency of
AM 1
0.01Hz
(Max. output frequency)
50.00Hz
–1200V
Model
depended
V/F curve setting of
motor 1
0: Straight-line V/F curve
1: Multi-point V/F curve
2: Torque-down V/F curve (power of 1.3)
3: Torque-down V/F curve (power of 1.7)
4: Torque-down V/F curve (power of 2.0)
5: Customized V/F curve (V/F separation)
0
Torque boost of motor 0.0%: (automatic)
0.0%