IPE300 series engineering VFD
Function parameter list
-244-
Function
code
Name
Description
Default
Modify
1: VFD stops when: the detected temperature
exceeds the overtemp threshold; the detected
resistance exceeds the overtemp protection
resistance; PTC selected by terminal function
is enabled; or the overtemp fault E-OHt is
reported.
P93.28
AIAO
disconnection
detection
0: Disable
1: Enable. When the disconnection is detected,
the fault A-OPn is reported and the action in
P93.29 is conducted.
0
○
P93.29
Run mode at
warning
0: Normal running
1: Decelerate to stop
0
○
P93.30
AIAO detected
temperature
compensation
value
-50.0°C
–50.0°C
0
○
P94 group
––Braking control functions
Function
code
Name
Description
Default Modify
P94.00
Brake enabling
0: Disable
1: Enable
0
◎
P94.01
Brake feedback
mode
0: With feedback signal
1: Without feedback signal
1
◎
P94.02
Brake release
frequency
Execute the release operation after the VFD
output frequency rises to the release frequency.
Range: 0.20
–20.00Hz
1.00Hz
○
P94.03
Releasing
current
Execute the release operation after the VFD
output current rises to the release current.
Range: 0.0
–P94.10
0.0%
○
P94.04
Delay time
before brake
release
Hold time before executing release operation.
Range: 0.000
–5.000s
0.3s
○
P94.05
Delay time after
brake release
Hold time after executing release operation.
Range: 0.000
–5.000s
0.3s
○
P94.06
Braking
frequency
Execute the brake switch-on operation after the
VFD output frequency drops to the braking
frequency.
Range: 0.20
–20.00Hz
1.00Hz
○