IPE300 series engineering VFD
Function parameter list
-120-
Functio
n code
Name
Description
Default Modify
power-off
re-powered on.
Output frequency
Running
Power off
Power on
Running
t
t1
t2
t1=P01.22
t2=P01.23
Setting range: 0.0
–3600.0s (Valid only when
=1)
P01.23
Start delay
After a VFD running command is given, the VFD
is in standby state and restarts with the delay
defined by
to implement brake release.
Setting range: 0.0
–600.0s
0.0s
○
P01.24 Stop speed delay 0.0
–600.0s
0.0s
○
P01.25
Open-loop 0Hz
output selection
0: Output without voltage
1: Output with voltage
2: Output with the DC braking current for stop
0
○
P01.26
DEC time for
emergency stop
0.0
–60.0s
2.0s
○
P01.27
Time of starting
segment of DEC S
curve
0.0
–50.0s
0.1s
◎
P01.28
Time of ending
segment of DEC S
curve
0.0
–50.0s
0.1s
◎
P01.29
Short-circuit
braking current
When the VFD starts in direct start mode
enter short-circuit braking.
During stop, if the running frequency of VFD is
lower than the starting frequency of brake for
stop (
to a non-zero value to
enter short-circuit braking for stop, and then carry
out DC braking in the time set by
. (See
descriptions for
setting range: 0.0
–150.0% (VFD)
setting range: 0.0
–50.0s
setting range: 0.0
–50.0s
0.0%
○
P01.30
Hold time of
short-circuit
braking for start
0.00s
○
P01.31
Hold time of
short-circuit
braking for stop
0.00s
○
P01.32
–
P01.34
Reserved