IPE300 series engineering VFD
Function parameter list
-144-
Function
code
Name
Description
Default Modify
P05.17
S3 switch-off
delay
Note:
After a virtual terminal is enabled, the state
of the terminal can be changed only in
communication
mode.
The
communication
address is 0x200A.
0.000s
○
P05.18
S4 switch-on
delay
0.000s
○
P05.19
S4 switch-off
delay
0.000s
○
P05.20
HDIA switch-on
delay
0.000s
○
P05.21
HDIA switch-off
delay
0.000s
○
P05.22
HDIB switch-on
delay
0.000s
○
P05.23
HDIB switch-off
delay
0.000s
○
P05.24
AI1 lower limit Used to define the relationship between the
analog input voltage and its corresponding
setting. When the analog input voltage exceeds
the range from the upper limit to the lower limit,
the upper limit or lower limit is used.
When the analog input is current input,
0mA
–20mA current corresponds to 0V–10V
voltage.
In different applications, 100.0% of the analog
setting corresponds to different nominal values.
See the descriptions of each application section
for details.
The following figure illustrates the cases of
several settings:
-100%
100%
Corresponding setting
AI
-10V
10V
20mA
0
AI2
AI1
Input filter time: to adjust the sensitivity of analog
0.00V
○
P05.25
Corresponding
setting of AI1
lower limit
0.0%
○
P05.26
AI1 upper limit
10.00V
○
P05.27
Corresponding
setting of AI1
upper limit
100.0%
○
P05.28
AI1 input filter
time
0.030s
○
P05.29
AI2 lower limit
-10.00
V
○
P05.30
Corresponding
setting of AI2
lower limit
-100.0
%
○
P05.31
AI2 middle value
1
0.00V
○
P05.32
Corresponding
setting of AI2
middle value 1
0.0%
○
P05.33
AI2 middle value
2
0.00V
○