IPE300 series engineering VFD
Function parameter list
-240-
P92 group
––Water supply functions
Function
code
Name
Description
Default Modify
P92.00
Sleep function for
water supply
0: Disable
1: Enable
0
◎
P92.01
Pressure
feedback source
0: AI1 set value
1: AI2 set value
2: AI3 set value
3: HDIA set value
4: HDIB set value
0
○
P92.02
Sleep check
mode
0: At a set frequency less than or equal to
1: At a feedback pressure greater than or equal
to
0
◎
P92.03
Sleep start
frequency
0.00
–P00.03 (Max. frequency)
10.00H
z
○
P92.04
Sleep start
pressure
0.00
–100.00%
50.0%
○
P92.05
Delayed entry
into sleep time
0.0
–3600.0s
5.0s
○
P92.06
Sleep wakeup
mode
0: At a set frequency greater than
1: At a feedback pressure less than
0
◎
P92.07
Sleep wakeup
frequency
0.00
–P00.03 (Max. frequency)
20.00H
z
○
P92.08
Set value of
sleep wakeup
pressure
0.00
–100.00%
10.0%
○
P92.09
Min. sleep time 0.0
–3600.0s
5.0s
○
P92.10
Auxiliary motor
selection
0: No auxiliary motor
1: Auxiliary motor 1
2: Auxiliary motor 2
3: Auxiliary motor 1 and 2
0
○
P92.11
Auxiliary motor 1
start/stop delay
time
0.0
–3600.0s
5.0s
○
P92.12
Auxiliary motor 2
start/stop delay
time
0.0
–3600.0s
5.0s
○