IPE300 series engineering VFD
Function parameter list
-226-
Function
code
Name
Description
Default Modify
P26.39
AO2 output
corresponding to
lower limit
value exceeds the allowed range, the output uses
the lower limit or upper limit.
When the analog output is current output, 1mA
equals 0.5V.
In different cases, the corresponding analog
output of 100% of the output value is different.
10V (20mA)
0.0%
100.0%
AO
Setting range of
: -100.0%
Setting range of
: 0.00V
–10.00V
–100.0%
setting range: 0.00V
–10.00V
setting range: 0.000s
–10.000s
setting range: -100.0%
setting range: 0.00V
–10.00V
–100.0%
setting range: 0.00V
–10.00V
setting range: 0.000s
–10.000s
0.00V
○
P26.40
AO2 output
upper limit
100.0%
○
P26.41
AO2 output
corresponding to
upper limit
10.00V
○
P26.42
AO2 output filter
time
0.000s
○
P26.43
AO3 output lower
limit
0.0%
○
P26.44
AO3 output
corresponding to
lower limit
0.00V
○
P26.45
AO3 output
upper limit
100.0%
○
P26.46
AO3 output
upper limit
10.00V
○
P26.47
AO3 output filter
time
0.000s
○
P26.48
–
P26.52
Reserved
0
–65535
0
○
P28 group
––Master/slave control
Function
code
Name
Description
Default Modify
P28.00
Master/slave
mode
0: Master/slave control is invalid.
1: The local device is the master.
2: The local device is the slave.
0
◎
P28.01
Master/slave
communication
data selection
0: CAN
1: RS485 (Reserved)
0
◎
P28.02
Master/slave
control
multifunction
mode
Ones place: Master/slave running mode
0: Master/slave mode 0
(Both the master and slave use speed control,
and power balancing is performed by droop
0x001
◎