Function parameter list
-175-
Function
code
Name
Description
Default
Modify
P11.04
Overvoltage
stalling
protection
voltage
120
–150% (standard bus voltage) (380V)
136%
○
120
–150% (standard bus voltage) (220V)
120%
P11.05
Current limit
mode
During accelerated running, as the load is
too large, the actual acceleration rate of
motor is lower than that of output frequency,
if no measures are taken, the VFD may trip
due to overcurrent during acceleration.
0x00
–0x11
Ones place: Current limit action
0: Invalid
1: Always valid
Tens place: Hardware current limit overload
alarm
0: Valid
1: Invalid
01
◎
P11.06
Automatic
current limit
threshold
Current-limit protection function detects
output current during running, and compares
it with the current-limit level defined by
, if it exceeds the current-limit level,
the VFD will run at stable frequency during
accelerated running, or run in decreased
frequency during constant-speed running; if
it
exceeds
the
current-limit
level
continuously, the VFD output frequency will
drop continuously until reaching lower limit
frequency. When the output current is
detected to be lower than the current-limit
level again, it will continue accelerated
running.
Output current A
Output frequency f
Current-limit
threshold
Set
frequency
Acceleration
Constant
speed
Time t
Time t
–200.0%
–50.00Hz/s
Type G:
160.0%
Type F:
120.0%
◎
P11.07
Frequency drop
rate during
current limit
10.00