IPE300 series engineering VFD
Function parameter list
-181-
Function
code
Name
Description
Default
Modify
P12.20
Stator resistance
of SM 2
0.001
–65.535Ω
Model
depended
○
P12.21
Direct-axis
inductance of SM
2
0.01
–655.35mH
Model
depended
○
P12.22
Quadrature-axis
inductance of SM
2
0.01
–655.35mH
Model
depended
○
P12.23
Counter-emf
constant of SM 2
0
–10000V
300
○
P12.24
Reserved
0
–0xFFFF
0x0000
●
P12.25
Reserved
0%
–50.0% (of the motor rated current)
10%
●
P12.26
Overload
protection of
motor 2
0: No protection
1:
Common
motor
(with
low-speed
compensation)
2:
Frequency-variable
motor
(without
low-speed compensation)
2
◎
P12.27
Overload
protection
coefficient of
motor 2
Motor overload multiples M=Iout/(In*K)
“In” is rated motor current, “Iout” is VFD
output current, “K” is motor overload
protection coefficient.
A smaller value of “K” indicates a bigger
value of “M”.
When M=116%, protection is performed after
motor overload lasts for 1 hour; when
M=200%, protection is performed after motor
overload lasts for 60 seconds; and when
M≥400%,
protection
is
performed
immediately.
1 min
1h
116 %
200 %
Time t
Motor overload multiples
Setting range: 20.0%
–120.0%
100.0%
○