-70-
Function
code
Name
Description
Default
Wait time for restart after
power-off
0.0
–3600.0s (valid when
is 1)
1.0s
Start delay
0.0
–60.0s
0.0s
Stop speed delay
0.0
–100.0s
0.0s
Open-loop 0Hz output
selection
0: Output without voltage
1: Output with voltage
2: Output with the DC braking current for
stop
0
DEC time for emergency
stop
0.0
–60.0s
2.0s
Time of starting segment of
DEC S curve
0.0
–50.0s
0.1s
Time of ending segment of
DEC S curve
0.0
–50.0s
0.1s
Short-circuit braking current 0.0
–150.0% (of the VFD rated current)
0.0%
Hold time of short-circuit
braking for start
0.00
–50.00s
0.00s
Hold time of short-circuit
braking for stop
0.00
–50.00s
0.00s
Digital input function
selection
1: Run forward
2: Run reversely
4: Jog forward
5: Jog reversely
6: Coast to stop
7: Reset faults
8: Pause running
21: ACC/DEC time selection 1
22: ACC/DEC time selection 2
30: Disable ACC/DEC
ACC time 2
0.0
–3600.0s
Model
depended
DEC time 2
0.0
–3600.0s
Model
depended
ACC time 3
0.0
–3600.0s
Model
depended
DEC time 3
0.0
–3600.0s
Model
depended