IPE300 series engineering VFD
Basic operation guidelines
-41-
The running command channel can be set by terminal commands besides
and
Channel of running
commands
Multifunction terminal
function 36
Switch the running
command channel to
keypad
Multifunction terminal
function 37
Switch the running
command channel to
terminal
Multifunction terminal
function 38
Switch the running
command channel to
communication
Keypad
/
Terminal
Communication
Terminal
Keypad
/
Communication
Communication
Keypad
Terminal
/
Note:
"/" indicates this multifunction terminal is invalid under present reference channel.
Related parameter list:
Function
code
Name
Description
Default
Speed control mode
0: Sensorless vector control (SVC) mode 0
1: Sensorless vector control (SVC) mode 1
2: Space voltage vector control mode
3: Closed-loop vector control mode
Note:
If 0, 1 or 3 is selected, it is required to carry
out motor parameter autotuning first.
2
Channel of running
commands
0: Keypad
1: Terminal
2: Communication
0
Communication
running command
Channel
0: Modbus
1: PROFIBUS/CANopen/DeviceNet
2: Ethernet
3: EtherCAT/Profinet
4: Programmable extension card
5: Wireless communication card
0
Motor parameter
autotuning
0: No operation
1: Rotary autotuning.
Comprehensive motor parameter autotuning. It is
recommended to use rotating autotuning when high
control accuracy is needed.
2: Static autotuning 1 (comprehensive autotuning);
static autotuning 1 is used in cases where the motor
cannot be disconnected from load.
3: Static autotuning 2 (partial autotuning); when the
present motor is motor 1, only
, and
0