IPE300 series engineering VFD
Function parameter list
-138-
Function
code
Name
Description
Default Modify
P04.50
End frequency
point for motor 1
switching off
IMVF mode
P04.44
–P00.03
25.00H
z
○
P04.51
End frequency
point for motor 2
switching off
IMVF mode
P04.49
–P00.03
25.00H
z
○
P05 group
––Input terminals
Function
code
Name
Description
Default Modify
P05.00
HDI input type
0x00
–0x11
Ones place: HDIA input type
0: HDIA is high-speed pulse input
1: HDIA is digital input
Tens place: HDIB input type
0: HDIB is high-speed pulse input
1: HDIB is digital input
0
◎
P05.01
Function of S1 0: No function
1: Run forward
2: Run reversely
3: Three-wire running control
4: Jog forward
5: Jog reversely
6: Coast to stop
7: Reset faults
8: Pause running
9: External fault input
10: Increase frequency setting (UP)
11: Decrease frequency setting (DOWN)
12: Clear the frequency increase/decrease
setting
13: Switch between A setting and B setting
14: Switch between combination setting and A
setting
15: Switch between combination setting and B
setting
1
◎
P05.02
Function of S2
2
◎
P05.03
Function of S3
7
◎
P05.04
Function of S4
0
◎
P05.05
Function of HDIA
0
◎
P05.06
Function of HDIB
0
◎