IPE300 series engineering VFD
Basic operation guidelines
-55-
Function
code
Name
Description
Default
communication
9: Ethernet communication
10: HDIB
11: EtherCat/Profinet communication
12: PLC
13: Reserved
Voltage set through
keypad
0.0%
–100.0% (of the motor rated voltage)
100.0%
–3600.0s
5.0s
Voltage decrease
time
0.0
–3600.0s
5.0s
Max. output voltage
–100.0% (of the motor rated voltage)
100.0%
Min. output voltage 0.0%
0.0%
Weakening coefficient
in constant power
zone
1.00
–1.30
1.00
Pull-in current 1 in SM
V/F control
When the SM VF control mode is enabled, the
function code is used to set the reactive current of
the motor when the output frequency is lower than
the frequency specified by
Setting range: -100.0%
–+100.0% (of the motor
rated current)
20.0%
Pull-in current 2 in SM
V/F control
When the SM VF control mode is enabled, the
function code is used to set the reactive current of
the motor when the output frequency is higher than
the frequency specified by
Setting range: -100.0%
–+100.0% (of the motor
rated current)
10.0%
Frequency threshold
for pull-in current
switching in SM V/F
control
When the SM VF control mode is enabled, the
function code is used to set the frequency threshold
for the switching between pull-in current 1 and
pull-in current 2.
Setting range: 0.00Hz
frequency)
50.00Hz
Reactive current
When the SM VF control mode is enabled, the
50