IPE300 series engineering VFD
Function parameter list
-115-
Function
code
Name
Description
Default
Modify
P00.17
VFD type
0: G type
1: P type
0
◎
P00.18
Function
parameter restore
0: No operation
1: Restore default values
2: Clear fault records
3: Lock keypad parameter
4. Reserved
5: Restore to default value (factory test mode)
6: Restore to default value (including motor
parameters)
Note:
After
the
selected
operation
is
performed, the function code is automatically
restored to 0. Restoring the default values may
delete the user password. Exercise caution
when using this function.
0
◎
P01 group
––Start and stop control
Functio
n code
Name
Description
Default Modify
P01.00
Start mode
0: Direct start
1: Start after DC braking
2: Speed tracking restart 1
3: Speed tracking restart 2
0
◎
P01.01
Starting frequency
of direct start
The function code indicates the initial frequency
during VFD start. See
(Starting frequency
hold time) for detailed information.
Setting range: 0.00
–50.00Hz
0.50Hz
◎
P01.02
Starting frequency
hold time
Output frequency
fmax
t1
T
F1 set by P01.01
f1
T1 set by P01.02
Setting a proper starting frequency can increase
the torque during VFD start. During the hold time
of the starting frequency, the output frequency of
the VFD is the starting frequency. And then, the
VFD runs from the starting frequency to the set
0.0s
◎