Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-52-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
starting
means the percentage of the rated current of the
inverter.
The setting range of P01.03: 0.0~100.0%
The setting range of P01.04: 0.00~50.00s
P01.05
ACC/DEC
selection
The changing mode of the frequency during start-up
and running.
0: Linear type
The output frequency increases or decreases linearly.
1: S curve type
The output frequency increases or decreases in S
curve.
S curve is suitable in the cases that require smooth
start-up and stop, such as elevators and conveyors.
0
◎
P01.06
S curve
start
proportion
0.0~50.0% (ACC/DEC time)
30.0%
◎
P01.07
S curve end
proportion
0.0~50.0% (ACC/DEC time)
30.0%
◎
P01.08
Stop mode
0: Decelerate to stop: after the stop command
becomes valid, the inverter decelerates to decrease
the output frequency during the set time. When the
0
○