Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-63-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P03.18
Upper
electromotion
torque
source
This function code is used to select the electromotion
and braking torque upper-limit setting source.
0: Keypad setting upper-limit frequency (P03.20 sets
P03.18, P03.21 sets P03.19)
1: AI1
2: AI2
3: AI3
4: HDI
5: Modbus communication
6~8: Reserved
Note: Setting modes 1~5,100% corresponds to
three times of the motor current.
0
○
P03.19
Upper
braking
torque
source
0
○
P03.20
Keypad
setting of
electromotion
torque
The function code is used to set the limit of the
torque.
Setting range: 0.0~300.0% (motor rated current)
180.0%
○
P03.21
Keypad
setting of
braking
torque
180.0%
○
P03.22
Weakening
coefficient in
constant
power zone
The function code is used when the motor is under
weakening control.
P03.22 and P03.23 are valid at constant power. The
motor will enter into the weakening state when the
motor runs at rated speed. Change the weakening
0.3
○
P03.23
Lowest
weakening
point in
constant
power zone
20%
○