Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-94-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
Setting range of P08.33: -100.0~100.0% (FDT1
electrical level)
Setting range of P08.34: 0.00~P00.03 (the Max.
frequency)
Setting range of P08.35: -100.0~100.0% (FDT2
electrical level)
P08.36
Frequency
arrival
detection
value
When the output frequency is among the positive or
negative detection range of the set frequency, the
multi-function digital output terminal will output the
signal of
“frequency arrival”, see the diagram below
for detailed information:
The setting range: 0.00Hz~P00.03 (the Max.
frequency)
0.00Hz
○
P08.37
Energy
braking
enable
This parameter is used to control the internal braking
pipe inside the inverter.
0: Disable
1: Enable
Note: Only apply to internal braking pipe.
0
○
P08.38
Threshold
voltage
After setting the original bus voltage to brake the
energy, adjust the voltage appropriately to brake the
load. The factory changes with the voltage level.
The setting range: 200.0~2000.0V
In order to prevent customers set the value is too
large, it is recommended setting range:
220V
voltage:
380.0V
○
380V
voltage:
700.0V