Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-115-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
feedback
detection time
detailed instruction of parameters
Setting range: 0.00~20.000s
P19.25
Contactor
feedback
detection time
0.00~20.000s
1.000s
◎
P19.26
Detection
time of torque
verification
fault
When the set values of torque verification current and
torque are non-zero, torque verification function is
valid. During running, if the output torque or current is
smaller than the set value and the hold time is larger
than P19.26, the inverter will stop because of torque
verification fault and the keypad will display TPF.
Setting range: 0.00~10.000s
0.500s
◎
P19.27
Detection
enabling at
joystick zero
position
The function codes are used for detection functions at
joystick zero position
When P19.27=1, detection enabling at joystick zero
position is valid. After the inverter stops, to avoid
restart of the inverter, make sure the joystick returns
to zero position (neutral position). The inverter can
restart only when the joystick returns to zero position
and the time is larger than P19.28.
Note: Signals at zero position are valid only under
joystick mode and hierarchical joystick mode.
Setting range of P19.27:
0: Disabled
1: Enabled
Setting range of P19.28: 0.000~60.000s
0
◎
P19.28
Delay time at
joystick zero
position
0.300s
◎
P19.29
Light load
acceleration
enabling
0: Disabled
1: Enabled
0
◎
P19.30
Reserved
●
P19.31
Torque
detection
value at FWD
0.0~150.0%
60.0%
◎