background image

Goodrive300-19 series open loop vector inverter special for hosit                                        Fault tracking

 

-196- 

Code   

Fault 

Cause 

Solution 

disconnected   

8.5.2 Other faults 

Code   

Fault   

Cause   

Solution   

PoFF 

System power 

failure 

The system is power-off or 

the bus voltage is too low 

Check the environment of the 

power supply 

 

Communication 

failure between 

keypad and main 

control board 

The keypad is not 

connected properly   

Check the installation 

environment of the keypad 

 

8.6 Common fault analysis 

8.6.1 The motor does not work 

The  motor does not 

rotate

If the POWER is on or not?

If there is displaying on the 

keypad

If the contactor closes on 

the input side 

Switch on the air 

contactor

Check the 

voltage of RST 
with multimeter

Inverter fault

Check the voltage of 

the power supply

If the keypad displays the 

information or not

Ensure the running 

command channel

Press RUN to run

Normal running 

Settle the fault 

according to the 
fault information 

Normal running 

Normal running

If the speed command 

setting is right or not 

Normal running 

Check the voltage of 

UVW with multimeter

Inverter fault 

If the motor configuration 

is right or not 

Set a right motor 

configuration

If the load is too heavy

Reduce the load if 

the motor is locked 

due to heavy load 

Motor fault 

Yes

No 

No 

Yes 

Yes 

Normal 

Yes 

Yes 

Normal 

Abnormal 

Normal

Communication 

Terminal 

Keypad 

Yes 

Abnormal 

No 

No 

No 

No 

No 

No 

Normal  

Normal 

Abnormal 

Yes

Normal 

Abnormal 

Yes 

Check the state of the input terminal 

Reset the 

parameters 

if it is normal running 

If the communication 

configuration is right or not 

If the communication 

parameter is right or not? 

Normal running 

Normal 

Abnormal

If the running is 

normal or not after 

switching on the 

terminal

Abnormal 

If the running is normal after setting 

a right speed command

 

Summary of Contents for Goodrive GD300-19-004G-4

Page 1: ...Series Open Loop Vector Inverter Special for Hoist Goodrive300 19 GD300 19 5R5G 4...

Page 2: ...reliability Goodrive300 19 inverters set the operating mode special for hoists which has safe and reliable brake logic and fault protection functions and built in functions in common use such as S cur...

Page 3: ...Installation confirmation 10 2 6 Basic commissioning 11 3 Product overview 12 3 1 What this chapter contains 12 3 2 Basic principles 12 3 3 Product specification 13 3 4 Name plate 15 3 5 Type designa...

Page 4: ...11 Digital input 159 7 12 Digital output 168 7 13 Multi step speed running 172 7 14 Fault handling 175 7 15 Hierarchical multi step speed running 180 7 16 Hoist operating mode 181 7 17 Brake control f...

Page 5: ...fications 230 A 4 Motor connection data 230 A 5 Applicable standards 231 A 6 EMC regualtions 232 Appendix B Dimension drawings 234 B 1 What this chapter contains 234 B 2 Keypad structure 234 B 3 Inver...

Page 6: ...vant requirements Note Physical hurt may occur if not follow relevant requirements Qualified electricians People working on the device should take part in professional electrical and safety training r...

Page 7: ...occur The base of the radiator may become hot during running Do not touch to avoid hurt The electrical parts and components inside the inverter are electrostatic Take measurements to avoid electrosta...

Page 8: ...connect all power supplies applied to the inverter before the terminal wiring and wait for at least the designated time on the inverter after disconnecting the power supply High voltage is present ins...

Page 9: ...bustible materials during maintenance and component replacement Do not carry out any isolation and pressure test on the inverter and do not measure the control circuit of the inverter by megameter Car...

Page 10: ...e plate is the correct type If not please contact with local dealers or company offices 5 Check to ensure the accessories including user s manual control keypad and extension card inside the device ar...

Page 11: ...the input power cables and motor cables meet the need of actual load 2 Check that the accessories of the inverter are correctly and properly installed The installation cables should meet the needs of...

Page 12: ...of the inverter according to the actual motor parameters 2 Autotuning If possible de coupled from the motor load to start dynamic autotuning Or if not static autotuning is available 3 Adjust the ACC...

Page 13: ...motors The diagram below shows the simplified main circuit diagram of the inverter The rectifier converts three phase AC voltage to DC voltage The capacitor bank of the intermediate circuit stabilize...

Page 14: ...nput current A Refer to the rated value Input frequency Hz 50Hz or 60Hz Allowed range 47 63Hz Power output Output voltage V 0 input voltage Output current A Refer to the rated value Output power kW Re...

Page 15: ...starting of the rotating motor Note 4kW the function is available Peripheral interface Terminal analog input resolution 20mV Terminal switch input resolution 2ms Analog input 2 AI1 AI2 0 10V 0 20mA an...

Page 16: ...9 standard products CE TUV IP20 will be identified on basis of actual certification Fig 3 3 Name plate 3 5 Type designation key The type designation contains information on the inverter The user can f...

Page 17: ...47 38 GD300 19 022G 4 22 56 45 GD300 19 030G 4 30 70 60 GD300 19 037G 4 37 80 75 GD300 19 045G 4 45 94 92 GD300 19 055G 4 55 128 115 GD300 19 075G 4 75 160 150 GD300 19 090G 4 90 190 180 GD300 19 110G...

Page 18: ...s 3 Keypad See Keypad operation procedure for detailed information 4 Cooling fan See Maintenance and hardware fault diagnosis for detailed information 5 Wiring port Connect to the control board and th...

Page 19: ...eries open loop vector inverter special for hosit Product overview 18 Serial No Name Illustration 12 Simple name plate See Model codes for detailed information 13 Lower cover Protect the internal part...

Page 20: ...ges the requirement our company will exempt from any responsibility Additionally if users do not comply with the suggestions some damage beyond the assured maintenance range may occur 4 2 Mechanical i...

Page 21: ...erials such as wood keep away from radioactive and flammable materials keep away from harmful gas and liquids be in sites with little salt keep away from direct sunlight Altitude 1000m If the sea leve...

Page 22: ...ting for the inverters of 380V 200kW c Floor mounting for the inverters of 380V 220 315kW Fig 4 2 Installation manner 1 Mark the hole location The location of the holes is shown in the dimension drawi...

Page 23: ...ig 4 3 Single installation Note The minimum space of B and C is 100mm 4 2 5 Multiple installations Parallel installation Fig 4 4 Parallel installation Note Before installing the inverters in different...

Page 24: ...vector inverter special for hosit Installation guidelines 23 4 2 6 Vertical installation Fig 4 5 Vertical installation Note Windscreen should be installed in vertical installation for avoiding mutual...

Page 25: ...oop vector inverter special for hosit Installation guidelines 24 4 2 7 Tilt installation Fig 4 6 Tilt installation Note Ensure the separation of the wind input and output channels in tilt installation...

Page 26: ...actor input filter output reactor output filter are optional parts Please refer to Peripheral Optional Parts for detailed information 2 A1 and A2 are optional parts 3 P1 and are short circuited in fac...

Page 27: ...ines 26 Fig 4 8 Terminals of main circuit for the inverters of 380V 1 5 2 2kW Fig 4 9 Terminals of main circuit for the inverters of 380V 4 5 5kW Fig 4 10 Terminals of main circuit for the inverters o...

Page 28: ...ecial for hosit Installation guidelines 27 Fig 4 12 Terminals of main circuit for the inverters of 380V 22 30kW Fig 4 13 Terminals of main circuit for the inverters of 380V 37 55kW Fig 4 14 Terminals...

Page 29: ...t of the main circuit 3 phase AC input terminals which are generally connected with the power supply U V W The inverter output 3 phase AC output terminals which are generally connected with the motor...

Page 30: ...ng conductor to the grounding terminal at the inverter and motor ends Braking resistor braking unit and DC reactor are optional parts Route the motor cable input power cable and control cables separat...

Page 31: ...Goodrive300 19 series open loop vector inverter special for hosit Installation guidelines 30 Fig 4 18 360 degree grounding technique 4 3 4 Wiring of control circuit Fig 4 19 Wiring of control circuit...

Page 32: ...Goodrive300 19 series open loop vector inverter special for hosit Installation guidelines 31 4 3 5 Terminals of control circuit Fig 4 20 Terminals of control circuit...

Page 33: ...Goodrive300 19 series open loop vector inverter special for hosit Installation guidelines 32...

Page 34: ...mode and the internal or external power supply The default setting is NPN internal mode Fig 4 21 U shaped contact tag If the signal is from NPN transistor please set the U shaped contact tag between...

Page 35: ...ecting the motor and motor cable in short circuit situations The inverter protects the motor and motor cable in a short circuit situation when the motor cable is dimensioned according to the rated cur...

Page 36: ...tuations for example if it is only used in soft start the inverter can be converted into power frequency running after starting and some corresponding bypass should be added Never connect the power su...

Page 37: ...parameters copy and 10 line high definition displaying of which the installation dimension is compatible with that of LED keypad 2 It is necessary to use M3 screw or installation bracket to fix the e...

Page 38: ...tate LED on means the inverter is in the remote communication control state TRIP LED for faults LED on when the inverter is in the fault state LED off in normal state LED blinking means the inverter i...

Page 39: ...e on the inverter in key operation mode Stop Reset key This key is used to stop in running state and it is limited by function code P07 04 This key is used to reset all control modes in the fault alar...

Page 40: ...ng speed output power output torque input terminals state output terminals state torque set value the current step of multi step speed AI1 AI2 AI3 HDI percentage of motor overload percentage of invert...

Page 41: ...n return to the second level menu from the third level menu The difference is pressing DATA ENT will save the set parameters into the control panel and then return to the second level menu with shifti...

Page 42: ...ting state 0 0 0 0 0 will be displayed Unless using the correct password the operators cannot enter it Set P07 00 to 0 to cancel password protection function The password protection becomes effective...

Page 43: ...Goodrive300 19 series open loop vector inverter special for hosit Keypad operation procedure 42 Fig 5 5 Sketch map of state watching...

Page 44: ...meter The fifth line Modify the modifying character of function codes the parameters can be modified or not and the modifying conditions below is the instruction means the set value of the parameter c...

Page 45: ...or accurate speed and torque control at all power ratings 2 SVPWM control mode No need to install encoders It can improve the control accuracy with the advantages of stable operation valid low frequen...

Page 46: ...nverter which is lower than or equal to the maximum frequency Setting range P00 05 P00 03 Max output frequency 50 00Hz P00 05 Lower limit of running frequency The lower limit of running frequency is t...

Page 47: ...0 19 series inverters provide 1 high speed pulse input as the standard configuration The pulse frequency range is 0 0 50 00kHz 100 0 of the high speed pulse input setting corresponds to the maximum fr...

Page 48: ...responds to the maximum output frequency 1 A frequency command 100 of B frequency setting corresponds to the maximum output frequency Select this setting if it needs to adjust on the base of A frequen...

Page 49: ...P00 12 0 0 3600 0s Depend on model P00 12 DEC time 1 Depend on model P00 13 Running direction 0 Runs at the default direction the inverter runs in the forward direction FWD REV indicator is off 1 Runs...

Page 50: ...ing switch loss increasing inverter temperature and the impact to the output capacity The inverter needs to derate on high carrier frequency At the same time the leakage and electrical magnetic interf...

Page 51: ...the whole procedure The auto adjusting function of the inverter can cancel the impact on the output voltage of the inverter because of the bus voltage fluctuation 1 P00 18 Function restore parameter 0...

Page 52: ...equency to increase the torque of the inverter during starting During the retention time of starting frequency the output frequency of the inverter is the starting frequency And then the inverter will...

Page 53: ...frequency during start up and running 0 Linear type The output frequency increases or decreases linearly 1 S curve type The output frequency increases or decreases in S curve S curve is suitable in th...

Page 54: ...close output and begin to carry on the DC braking after the waiting time This function is used to avoid the overcurrent fault caused by DC braking when the speed is too high Stop DC braking current t...

Page 55: ...fter the speed reaches P01 15 and delays for P01 24 2 P01 15 Stopping speed 0 00 100 00Hz 0 50Hz P01 16 Detection of stopping speed 0 Detect according to speed setting no stopping delay 1 Detect accor...

Page 56: ...e initialization Note This function should be selected with cautions or serious result may follow 0 P01 19 Action if running frequency lower limit frequency valid 0 This function code determines the r...

Page 57: ...ter waiting for the time defined by P01 22 0 P01 22 The waiting time of restart after power off The function determines the waiting time before the automatic running of the inverter when powering off...

Page 58: ...d standard adaptive motor have a great gap control performance will decrease obviously Note Resetting P02 01 can initialize P02 02 P02 10 Depend on model P02 02 Rated frequency of asynchronous motor 1...

Page 59: ...motor 1 0 1 6553 5mH Depend on model P02 10 Non load current of asynchronous motor 1 0 1 6553 5A Depend on model P02 11 Magnetic saturation coefficient 1 for the iron core of AM1 0 0 100 0 80 0 P02 1...

Page 60: ...the heat releasing effect of the specific motors will not be impacted by the rotation speed it is not necessary to adjust the protection value during low speed running P02 27 Motor 1 overload protect...

Page 61: ...amic response performance of vector control speed loop Increasing the proportional gain and decreasing the integral time can speed up the dynamic response of the speed loop But too high proportional g...

Page 62: ...fficient of braking slip 100 P03 09 Current loop percentage coefficient P Note 1 These two parameters adjust the PI adjustment parameter of the current loop which affects the dynamic response speed an...

Page 63: ...P03 16 sets P03 14 P03 17 sets P03 15 1 AI1 2 AI2 3 AI3 4 Pulse frequency HDI setting upper limit frequency 5 Multi step setting upper limit frequency 6 Modbus communication setting upper limit freque...

Page 64: ...Note Setting modes 1 5 100 corresponds to three times of the motor current 0 P03 19 Upper braking torque source 0 P03 20 Keypad setting of electromotion torque The function code is used to set the li...

Page 65: ...agnetic field inside the inverter to improve the torque performance during the starting process The setting time 0 000 10 000s 0 300s P03 26 Weak magnetic proportional gain 0 8000 Note P03 24 P03 26 a...

Page 66: ...adjusted through the frequency reference channel set by P00 06 or the voltage reference channel set by P04 27 to change the feature of the curve Note Vb in the below picture is the motor rated voltage...

Page 67: ...n P04 00 1 the user can set V F curve through P04 03 P04 08 V F is generally set according to the load of the motor Note V1 V2 V3 f1 f2 f3 Too high low frequency voltage will heat the motor excessivel...

Page 68: ...f which fb is the rated frequency of the motor its function code is P02 02 n is the rated rotating speed of the motor and its function code is P02 03 p is the pole pair of the motor 100 0 corresponds...

Page 69: ...election can be selected by defined channels in P08 31 or terminal function 35 the shift between motor 1 and motor 2 P04 14 Torque boost of motor 2 0 0 P04 15 Torque boost close of motor 2 20 0 P04 16...

Page 70: ...old of motor 2 30 00Hz P04 26 Energy saving operation 0 No operation 1 Automatic energy saving operation Motors will automatically adjust the output voltage to save energy at light loads 0 P04 27 Volt...

Page 71: ...he output voltage The setting range of P04 31 P04 32 100 0 the rated voltage of the motor The setting range of P04 32 0 0 P04 31 100 0 P04 32 Minimum output voltage 0 0 P04 33 Weakening coefficient in...

Page 72: ...speed terminal 3 19 Multi step speed terminal 4 20 Multi step speed pause 21 ACC DEC time 1 22 ACC DEC time 2 23 28 Reserved 29 Torque control disabling 30 ACC DEC disabling 31 Reserved 32 Reserved 3...

Page 73: ...rminal is cathode BIT8 BIT7 BIT6 BIT5 HDI S8 S7 S6 BIT4 BIT3 BIT2 BIT1 BIT0 S5 S4 S3 S2 S1 The setting range 0x000 0x1FF 0x000 P05 11 ON OFF filter time Set the sampling filter time of S1 S8 and HDI t...

Page 74: ...K1 K2 Running command K1 K2 OFF OFF OFF OFF ON ON ON ON Stop Hold FWD running REV running 2 3 wire control 1 SIn is the enabling terminal on this mode and the running command is caused by FWD and the...

Page 75: ...terminal control see P07 04 P05 14 Switch on delay of S1 terminal The function code defines the corresponding delay time of electrical level of the programmable input terminals from switching on to sw...

Page 76: ...terminal 0 000s P05 28 Switch on delay of S8 terminal 0 000s P05 29 Switch off delay of S8 terminal 0 000s P05 30 Switch on delay of HDI terminal 0 000s P05 31 Switch off delay of HDI terminal 0 000s...

Page 77: ...ting range of P05 32 0 00V P05 34 The setting range of P05 33 100 0 100 0 The setting range of P05 34 P05 32 10 00V The setting range of P05 35 100 0 100 0 The setting range of P05 36 0 000s 10 000s T...

Page 78: ...47 Correspondin g setting of the upper limit of AI3 100 0 P05 48 AI3 input filter time 0 100s P05 49 HDI high speed pulse input function selection The function selection when HDI terminals is high sp...

Page 79: ...mation of the related functions 0 P06 01 Y output 0 Invalid 1 In operation 2 Forward rotation operation 3 Reverse rotation operation 4 Jogging operation 5 Inverter fault 6 Frequency degree test FDT1 7...

Page 80: ...nal is negative BIT3 BIT2 BIT1 BIT0 RO2 RO1 HDO Y Setting range 00 0F 00 P06 06 Y switch on delay time The function code defines the corresponding delay time of the electrical level change during the...

Page 81: ...ommunication set value 2 16 21 Reserved 22 Torque current relative to 3 times of the rated current of the motor 23 Pre magnetizing current relative to the rated current of the motor 24 30 Reserved 0 P...

Page 82: ...100 0 P06 29 Setting range of P06 28 0 00 50 00kHz Setting range of P06 29 P06 27 100 0 Setting range of P06 30 0 00 50 00kHz Setting range of P06 31 0 000s 10 000s P06 21 AO1 output filter time 0 000...

Page 83: ...input right password the operator cannot enter into it Note Restoring to the default value can clear the password please use it with caution P07 01 Parameter copy The function code determines the man...

Page 84: ...commands 7 Quick commission mode commission according to the non factory parameter Note Press QUICK JOG to shift between forward rotation and reverse rotation the inverter does not remember the state...

Page 85: ...tput torque on BIT8 BIT9 reserved BIT10 input terminals state BIT11 output terminals state BIT12 torque set value on BIT13 BIT14 reserved BIT15 the current stage in multi step speed 0x03FF P07 06 Para...

Page 86: ...ing frequency P07 08 1 00 P07 09 Rotation speed coefficient 0 1 999 9 Mechanical rotation speed 120 displayed running frequency P07 09 motor pole pairs 100 0 P07 10 Linear speed coefficient 0 1 999 9...

Page 87: ...9 kWh P07 17 Reserved Reserved P07 18 Rated power of the inverter 0 4 3000 0kW P07 19 Rated voltage of the inverter 50 1200V P07 20 Rated current of the inverter 0 1 6000 0A P07 21 Factory bar code 1...

Page 88: ...13 Input side phase loss SPI 14 Output side phase loss SPO 15 Overheat of the rectifier module OH1 16 Overheat fault of the converter module OH2 17 External fault EF 18 485 communication fault CE 19...

Page 89: ...41 Brake feedback fault FAE 42 Torque verification fault TPF 43 Joystick zero fault STC 44 Hierarchical reference fault STEP 45 Analog speed reference deviation fault AdE P07 33 Running frequency at...

Page 90: ...P07 40 Output terminals state at current fault 0 P07 41 Running frequency at previous fault 0 00Hz P07 42 Ramp reference frequency at previous fault 0 00Hz P07 43 Output voltage at previous fault 0V...

Page 91: ...Output terminals state at previous fault 0 P07 49 Running frequency at previous 2 fault 0 00Hz P07 50 Ramp reference frequency at previous 2 faults 0 00Hz P07 51 Output voltage at previous 2 faults 0...

Page 92: ...e is the factory default one Setting range 0 0 3600 0s Depend on model P08 01 DEC time 2 Depend on model P08 02 ACC time 3 Depend on model P08 03 DEC time 3 Depend on model P08 04 ACC time 4 Depend on...

Page 93: ...requency range 2 0 00Hz P08 13 Jumping frequency 3 0 00Hz P08 14 Jumping frequency range 3 0 00Hz P08 27 Set running time Pre set running time of the inverter When the accumulative running time achiev...

Page 94: ...4 Reserved LED tens shifting enabling in operation 0 Disabled 1 Enabled 0x00 P08 32 FDT1 electrical level detection value When the output frequency exceeds the corresponding frequency of FDT electric...

Page 95: ...tion digital output terminal will output the signal of frequency arrival see the diagram below for detailed information The setting range 0 00Hz P00 03 the Max frequency 0 00Hz P08 37 Energy braking e...

Page 96: ...arrier frequency limit mode 0 Low speed carrier frequency limit mode 1 the carrier frequency will limit to 2k if it exceeds 2k at low speed 1 Low speed carrier frequency limit mode 2 the carrier frequ...

Page 97: ...thousands key and digital potentiometer integral function 0 The integral function is valid 1 The integral function is invalid P08 43 Integral ratio of keypad potentiometer 0 01 10 00s 0 10s P08 44 UP...

Page 98: ...undreds Reserved 0x000 P08 48 High bit of initial power consumption This parameter is used to set the original value of the power consumption Original value of power consumption P08 48 1000 P08 49 Set...

Page 99: ...nt of the AC input side Setting range 0 00 1 00 0 56 P10 Group Multi step speed control P10 02 Multi step speed 0 The frequency setting range of stage 0 15 100 0 100 0 100 0 of the frequency setting c...

Page 100: ...n terminal 1 terminal 2 terminal 3 terminal 4 and multi step speed is as following Terminal 1 OFF ON OFF ON OFF ON OFF ON Terminal 2 OFF OFF ON ON OFF OFF ON ON Terminal 3 OFF OFF OFF OFF ON ON ON ON...

Page 101: ...ake the inverter generate power again The returning power can maintain the bus voltage to ensure a rated running of the inverter until the recovery of power Voltage degree 220V 380V 660V Frequency dec...

Page 102: ...ut current and compare it with the limit level defined in P11 06 If it exceeds the level the inverter will run at stable frequency in ACC running or the inverter will derate to run during the constant...

Page 103: ...to the rated current of the inverter LED tens 0 The inverter continues to work after underload pre alarm 1 The inverter continues to work after underload pre alarm and the inverter stops to run after...

Page 104: ...e action of fault output terminals on undervoltage and fault reset 0x00 0x11 LED ones 0 Action under fault undervoltage 1 No action under fault undervoltage LED tens 0 Action during the automatic rese...

Page 105: ...ding to the standard principles if the gap between the motor and the standard one is huge the control performance of the inverter will decrease Note Resetting P12 01 can initialize P12 02 P12 05 Depen...

Page 106: ...6553 5mH Depend on model P12 09 Mutual inductance of asynchronous motor 2 0 1 6553 5mH Depend on model P12 10 Non load current of asynchronous motor 2 0 1 6553 5A Depend on model P12 11 Magnetic satu...

Page 107: ...l be reported after 1 hour when M 200 the fault will be reported after 1 minute when M 400 the fault will be reported instantly Setting range 20 0 120 0 100 0 P12 28 Correction coefficient of motor 2...

Page 108: ...ll slaves on the Modbus fieldbus can receive the frame but the salve does not answer The communication of the drive is unique in the communication net This is the fundamental for the point to point co...

Page 109: ...after the system deals with the data wait until achieving the answer delay time to send the data to the upper computer 5 P14 04 Fault time of communicatio n overtime 0 0 invalid 0 1 60 0s When the fu...

Page 110: ...00Hz P00 03 0 00Hz P17 01 Output frequency Display current output frequency of the inverter Range 0 00Hz P00 03 0 00Hz P17 02 Ramp reference frequency Display current ramp reference frequency of the i...

Page 111: ...e of the inverter Range 0000 00FF 0 P17 13 Digital output terminals state Display current switch output terminals state of the inverter Range 0000 000F 0 P17 14 Digital adjustment Display the adjustme...

Page 112: ...00 0 300 0 the rated current of the motor 0 0 P17 32 Magnetic flux linkage Display the magnetic flux linkage of the motor Range 0 0 200 0 0 0 P17 33 Exciting current reference Display the exciting cur...

Page 113: ...meter mode Users can select the mode on basis of actual conditions See the standard wiring diagrams and function code settings corresponding to the modes in Chapter 7 It only needs to set P19 00 to me...

Page 114: ...ON Hierarchical reference terminal 2 OFF OFF ON ON ON ON Hierarchical reference terminal 3 OFF OFF OFF ON ON ON Hierarchical reference terminal 4 OFF OFF OFF OFF ON ON Hierarchical reference terminal...

Page 115: ...9 16 REV switching off current 0 0 P19 17 REV switching off torque 0 0 P19 18 Switching off hold frequency Refer to brake control function in Chapter 7 for detailed instruction of parameters Setting r...

Page 116: ...d the keypad will display TPF Setting range 0 00 10 000s 0 500s P19 27 Detection enabling at joystick zero position The function codes are used for detection functions at joystick zero position When P...

Page 117: ...vector inverter special for hosit Function parameters 116 Function code Name Detailed instruction of parameters Default value Modify light load acceleration P19 32 Torque detection value at REV light...

Page 118: ...ring on Check before powering on Please check according to the installation list in Chapter 2 Original powering operation Check to ensure there is no mistake in wiring and power supply switch on the a...

Page 119: ...verter special for hosit Basic operation instruction 118 Note If a fault occurs please do as Fault Tracking to judge the reason and settle the issue Besides P00 01 terminal command setting can also be...

Page 120: ...unction terminal is invalid on the current reference channel Relative parameters table Function code Name Detailed instruction of parameters Default value P00 00 Speed control mode 1 Sensorless vector...

Page 121: ...t the command to the terminal 38 Shift the command to the communication P07 01 Parameter copy The function code determines the manner of parameters copy 0 No operation 1 Upload the local function para...

Page 122: ...otor and torque current the current heft generating torque by controlling and measuring the stator current vector according to the principles of beamed magnetic field to control the range and phase of...

Page 123: ...iV iW UV UW Uu iM iT 1wr 1wr iT R S T Function code Name Detailed instruction of parameters Default value P00 00 Speed control mode 1 Sensorless vector control mode 1 2 SVPWM control mode 1 P00 15 Mo...

Page 124: ...urrent loop integral coefficient I 0 65535 1000 P03 11 Torque setting method 0 Torque control is invalid 1 Keypad setting torque P03 11 2 Analog AI1 setting torque 3 Analog AI2 setting torque 4 Analog...

Page 125: ...rresponds to the maximum frequency P03 15 Upper frequency of reverse rotation in torque control 0 Keypad set by P03 17 1 9 The same as P03 14 0 P03 16 Keypad setting for upper frequency of forward rot...

Page 126: ...3 P03 23 Lowest weakening point in constant power zone 10 100 20 P03 24 Max voltage limit 0 0 120 0 100 0 P03 25 Pre exciting time 0 000 10 000s 0 300s P17 32 Magnetic flux linkage 0 0 200 0 0 0 7 4 S...

Page 127: ...e middle dots The whole curve consists of 5 dots The starting dot is 0Hz 0V and the ending dot is the basic frequency of the motor the rated voltage of the motor During the setting processing 0 f1 f2...

Page 128: ...mpensation gain internal output adjustment can be set to compensate the speed change caused by load fluctuation Setting range of slip compensation gain 0 200 of which 100 corresponds to the rated slip...

Page 129: ...Goodrive300 19 series open loop vector inverter special for hosit Basic operation instruction 128...

Page 130: ...verter Function code Name Detailed instruction of parameters Default value P00 00 Speed control mode 1 Sensorless vector control mode 1 2 SVPWM control mode 1 P00 03 Max output frequency P00 04 400 00...

Page 131: ...motor 1 0 00Hz P04 05 0 00Hz P04 04 V F voltage 1 of motor 1 0 0 110 0 00 0 P04 05 V F frequency 2 of motor 1 P04 03 P04 07 00 00Hz P04 06 V F voltage 2 of motor 1 0 0 110 0 00 0 P04 07 V F frequency...

Page 132: ...ower low torque V F curve 5 Customized V F V F separation 0 P04 14 Torque boost of motor 2 0 0 automatic 0 1 10 0 0 0 P04 15 Torque boost close of motor 2 0 0 50 0 rated frequency of motor 1 20 0 P04...

Page 133: ...0 P04 25 Vibration control threshold of motor 2 0 00Hz P00 03 the Max frequency 30 00Hz P04 26 Energy saving operation 0 No operation 1 Automatic energy saving operation 0 P04 27 Voltage setting 0 Key...

Page 134: ...rs support two kinds of control mode torque control and rotation speed control The core of rotation speed is that the whole control focuses on the stable speed and ensures the setting speed is the sam...

Page 135: ...Goodrive300 19 series open loop vector inverter special for hosit Basic operation instruction 134...

Page 136: ...ing torque the same as above 6 Multi step torque setting the same as above 7 Modbus communication setting torque the same as above 8 10 Reserved 0 P03 12 Keypad setting torque 300 0 300 0 rated curren...

Page 137: ...per frequency of forward rotation 0 00 Hz P00 03 the Max output frequency 50 00Hz P03 17 Keypad setting for upper frequency of reverse rotation 0 00 Hz P00 03 the Max output frequency 50 00Hz P03 18 U...

Page 138: ...se check the safety of surrounding environment of the motor and the load before autotune The power is still applied even when the motor stops running during static autotune Please do not touch the mot...

Page 139: ...Reserved Start Select running command channel P00 01 Select the shifting channel between motor 1 and motor 2 P08 31 Terminal function 35 Shift motor 1 to motor 2 Communication set value 2009H Motor 1...

Page 140: ...and empty state otherwise the result of autotune is incorrect The asynchronous motors can autotune the parameters of P02 06 P02 10 3 During the motor autotune if static autotune is selected do not de...

Page 141: ...y 0 P02 01 Rated power of asynchronous motor 1 0 1 3000 0kW Depend on model P02 02 Rated frequency of asynchronous motor 1 0 01Hz P00 03 the Max frequency 50 00Hz P02 03 Rated speed of asynchronous mo...

Page 142: ...ction digital input terminal 35 Shift the motor 1 to motor 2 P08 31 Motor shifting LED ones shifting channel 0 Terminal shifting 1 Modbus communication shifting 2 4 Reserved 0 P12 00 Motor 2 type 0 As...

Page 143: ...and stop control of the inverter includes three states start after the running command during normal powering on start after the restarting function becomes valid during normal powering on and start a...

Page 144: ...ve300 19 series open loop vector inverter special for hosit Basic operation instruction 143 2 The starting logic figure of starting after the restarting function becomes valid during the normal poweri...

Page 145: ...arting after the automatic fault reset Inverter fault In running Fault reset times of the inverter P08 28 Interval time of automatic fault reset of the inverter P08 29 Fault reset and the inverter sta...

Page 146: ...e type 0 P01 06 S curve start proportion 0 0 50 0 ACC DEC time 30 0 P01 07 S curve end proportion 0 0 50 0 ACC DEC time 30 0 P01 08 Stop mode 0 Decelerate to stop 1 Coast to stop 0 P01 09 Starting fre...

Page 147: ...d is invalid when powering on 1 The terminal running command is valid when powering on 0 P01 19 Action if running frequency lower limit frequency valid 0 0 Run at the lower limit frequency 1 Stop 2 Hi...

Page 148: ...del P08 01 DEC time 2 0 0 3600 0s Depend on model P08 02 ACC time 3 0 0 3600 0s Depend on model P08 03 DEC time 3 0 0 3600 0s Depend on model P08 04 ACC time 4 0 0 3600 0s Depend on model P08 05 DEC t...

Page 149: ...pad AI1 Reserved MODBUS Reserved Multi step speed Reserved HDI AI3 AI2 Hierarchical multi step speed reference UP terminal DOWN terminal Digital potentiometer P08 43 tens setting frequency control sel...

Page 150: ...nce channel When select multi function terminal UP 10 and DOWN 11 to set the internal assistant frequency P08 44 and P08 45 can be set to increase or decrease the set frequency quickly Sx Sy UP termin...

Page 151: ...eypad 1 AI1 2 AI2 3 AI3 4 High speed pulse HDI setting 5 Reserved 6 Multi step speed running setting 7 Reserved 8 Modbus communication setting 9 12 Reserved 13 Hierarchical multi step speed reference...

Page 152: ...peed when multi step speed has the priority LED hundreds action selection during stopping 0 Setting is valid 1 Valid during running clear after stopping 2 Valid during running clear after receiving th...

Page 153: ...ng frequency 0 00Hz P00 03 Max output frequency 0 00Hz P17 02 Ramp reference frequency 0 00Hz P00 03 Max output frequency 0 00Hz P17 14 Digital adjustment 0 00Hz P00 03 0 00Hz 7 9 Analog input Goodriv...

Page 154: ...HDI P05 00 0 HDI is high speed pulse input 1 HDI is switch input P05 49 0 frequency setting input 1 counter input 2 length counter input Analog curve input setting Analog input filter Relative parame...

Page 155: ...t filter time 0 000s 10 000s 0 100s P05 42 Lower limit of AI3 10 00V P05 44 10 00V P05 43 Corresponding setting of the lower limit of AI3 100 0 100 0 100 0 P05 44 Middle value of AI3 P05 42 P05 46 0 0...

Page 156: ...0kHz 50 00kHz P05 53 Corresponding setting of HDI upper limit frequency 100 0 100 0 100 0 P05 54 HDI frequency input filter time 0 000s 10 000s 0 010s 7 10 Analog output Goodrive300 19 series inverter...

Page 157: ...ted synchronous rotation speed of the motor 4 Output current relative to the inverter 0 2 times of the rated current of the inverter 5 Output current relative to the motor 0 2 times of the rated curre...

Page 158: ...Reserved Relative parameters list Function code Name Detailed instruction of parameters Default value P06 00 HDO output 0 Open collector high speed pulse output 1 Open collector output 0 P06 14 AO1 ou...

Page 159: ...0V P06 19 Upper output limit of AO1 P06 17 100 0 100 0 P06 20 Corresponding AO1 output of upper limit 0 00V 10 00V 10 00V P06 21 AO1 output filter time 0 000s 10 000s 0 000s P06 22 Lower output limit...

Page 160: ...n the standard configuration All functions of the digital input terminals are programmable by the function codes Open collector input terminal can be selected into high speed pulse input terminal or c...

Page 161: ...o position signal 17 Multi step speed terminal 2 61 Hierarchical reference terminal 1 18 Multi step speed terminal 3 62 Hierarchical reference terminal 2 19 Multi step speed terminal 4 63 Hierarchical...

Page 162: ...to stop in P01 08 and usually used in remote control 7 Fault reset External fault reset It has the same function with the reset function of STOP RST on the keypad This function can realize remote fau...

Page 163: ...1 The 16 stage speeds can be set by the combination of digital state of four terminals Note Multi step speed 1 is the low bit multi step speed 4 is the high bit Multi step speed 4 Multi step speed 3...

Page 164: ...omes valid the running command channel will be shifted into keypad running command channel and the running command channel will come back to the original state if the function terminal is invalid 37 S...

Page 165: ...wrong the inverter will alarm brake feedback fault FAE 60 Joystick zero position signal After the inverter stops to avoid restart of the inverter make sure the joystick returns to zero position neutra...

Page 166: ...13 Shift between A setting and B setting 14 Shift between combination setting and A setting 15 Shift between combination setting and B setting 16 Multi step speed terminal 1 17 Multi step speed termi...

Page 167: ...rence terminal 2 63 Hierarchical reference terminal 3 64 Hierarchical reference terminal 4 65 Hierarchical reference terminal 5 P05 10 Polarity selection of input terminals 0x000 0x1FF 0x000 P05 11 ON...

Page 168: ...on delay of S4 terminal 0 000 50 000s 0 000s P05 21 Switch off delay of S4 terminal 0 000 50 000s 0 000s P05 22 Switch on delay of S5 terminal 0 000 50 000s 0 000s P05 23 Switch off delay of S5 termin...

Page 169: ...0 7 12 Digital output Goodrive300 19 series inverters have 2 relay output terminals 1 open collector Y output terminal and 1 high speed pulse output terminal in the standard configuration All functio...

Page 170: ...Function Instruction 0 Invalid The output terminal has no function 1 In operation Output ON signal when the inverter is running and there is frequency output 2 Forward rotation operation Output ON sig...

Page 171: ...08 P11 10 for the detailed instruction 15 Underload pre alarm Output ON signal if the inverter is beyond the pre alarm point Refer to P11 11 P11 12 for the detailed instruction 16 21 Reserved 22 Runn...

Page 172: ...6 00 HDO output 0 Open collector high speed pulse output 1 Open collector output 0 P06 01 Y output 0 Invalid 1 In operation 2 Forward rotation operation 3 Reverse rotation operation 4 Jogging operatio...

Page 173: ...0 50 000s only valid when P06 00 1 0 000s P06 10 RO1 switch on delay time 0 000 50 000s 0 000s P06 11 RO1 switch off delay time 0 000 50 000s 0 000s P06 12 RO2 switch on delay time 0 000 50 000s 0 000...

Page 174: ...erminal function 18 Multi step speed terminal 3 Terminal function 19 Multi step speed terminal 4 Multi step speed 15 Multi step speed Terminal function 16 Multi step speed terminal 1 Terminal function...

Page 175: ...ti step speed 5 100 0 100 0 0 0 P10 14 Multi step speed 6 100 0 100 0 0 0 P10 16 Multi step speed 7 100 0 100 0 0 0 P10 18 Multi step speed 8 100 0 100 0 0 0 P10 20 Multi step speed 9 100 0 100 0 0 0...

Page 176: ...te the best reason Rerunning Normal running Settle the fault consult INVT Y N N Y Relative parameters list Function code Name Detailed instruction of parameters Default value P07 27 Current fault type...

Page 177: ...g unit fault bCE 24 Running time arrival END 25 Electrical overload OL3 26 Panel communication fault PCE 27 Parameter uploading fault UPE 28 Parameter downloading fault DNE 29 31 Reserved 32 Grounding...

Page 178: ...ous 4 fault type P07 32 Previous 5 fault type P07 33 Running frequency at current fault 0 00Hz P07 34 Ramp reference frequency at current fault 0 00Hz P07 35 Output voltage at current fault 0V P07 36...

Page 179: ...at previous fault 0 00Hz P07 42 Ramp reference frequency at previous fault 0 00Hz P07 43 Output voltage at previous fault 0V P07 44 Output current at previous fault 0 0A P07 45 Bus voltage at previou...

Page 180: ...value fault P07 50 Ramp reference frequency at previous 2 faults 0 00Hz P07 51 Output voltage at previous 2 faults 0V P07 52 Output current at previous 2 fault 0 0A P07 53 Bus voltage at previous 2 fa...

Page 181: ...0 ON ON ON ON ON Hierarchical reference 5 P19 11 Note Only when all lower hierarchical references close can the upper hierarchical references close Generally set hierarchical reference 0 to 0 0 Set sp...

Page 182: ...Remote control mode 3 Hierarchical joystick mode 4 Hierarchical remote control mode 5 Electromotion potentiometer mode 0 P19 06 Hierarchical multi step speed reference 0 0 0 100 0 0 0 P19 07 Hierarch...

Page 183: ...r FWD running S1 Frequency reference Keypad REV running S2 Fault reset S3 RO1 Motor in running RO2 Fault output AO1 Running frequency AO2 Set frequency The mode is used when I O signal setting and fun...

Page 184: ...the defined time in P19 28 When P19 27 1 detection enabling at joystick zero position is valid When the joystick returns to zero postion if the detected speed reference AI1 by the inverter is larger...

Page 185: ...d is given by AI1 and the forward and reverse direction signals of the hoist are given by S1 and S2 For remote control mode joystick zero position detection is invalid The parameters of remote control...

Page 186: ...reference of multi step speed terminals The mode supports up to 6 different speed levels 1 contact at the 1st speed level 5 contacts at other speed levels given by direction command The hierarchical c...

Page 187: ...Joystick zero position signal P06 03 Relay RO1 output 5 Fault output P06 04 Relay RO2 output 34 Brake control output P06 14 AO1 output 0 Running frequency P06 15 AO2 output 5 Current output P19 01 Bra...

Page 188: ...channel LED flickering P00 06 A frequency command 13 Hierarchical multi step speed reference P05 01 S1 terminal function selection 1 Forward rotation operation FWD P05 02 S2 terminal function selectio...

Page 189: ...signal is given again the inverter will continue accelerating toward 100 speed The DEC command goes similar to the ACC command If the direction command is canceled the inverter will decelerate toward...

Page 190: ...t signal is switching on After receiving the running command the inverter will accelerate to P19 18 and simultaneously it will start torque verification When confirming torque verification is OK condi...

Page 191: ...light When the fault has been removed the motor can be restarted 8 4 Fault history Function codes P07 25 P07 30 store 6 recent faults Function codes P07 31 P07 38 P07 39 P7 46 P07 47 P07 54 show drive...

Page 192: ...Accelerating overcurrent 1 The acceleration or deceleration is too fast 2 The voltage of the grid is too low 3 The power of the inverter is too low 4 The load transients or is abnormal 5 The grounding...

Page 193: ...oss U V W phase loss output or three phases of the load are seriously asymmetrical Check the output distribution Check the motor and cable OH1 Rectifying module overheat Air duct jam or fan damage Amb...

Page 194: ...e to EEPROM Press STOP RST to reset Change the main control board bCE Braking unit fault Braking circuit fault or damage to the braking pipes The external braking resistor is not sufficient Check the...

Page 195: ...in the keypad ETH1 Grounding shortcut fault 1 The output of the inverter is short circuited with the ground There is fault in the current detection circuit The actual motor power sharply differs from...

Page 196: ...Brake feedback fault The brake feedback circuit is offline or the connection is not good The brake feedback detection time is too short Check the brake feedback circuit Increase the detection time P19...

Page 197: ...the information or not Ensure the running command channel Press RUN to run Normal running Settle the fault according to the fault information Normal running Normal running If the speed command settin...

Page 198: ...if there is abnormal fluctuation to the load Check if there is abnormal vibration to frequency reference Check the speed loop and current loop are right or not Vector control or not Perform parameter...

Page 199: ...eck if shortening the ACC DEC time is allowed Check if it needs to use the options Add braking options Adjust the braking options and the resistance Yes No Yes No Yes No Yes No Yes No Yes Yes 8 6 4 Un...

Page 200: ...erter runs at low speed all the time Select right motor Low the load Change the motor Set proper carrier frequency Add output filter If it is the inverter fault please contact with our company Yes No...

Page 201: ...low 8 6 7 Motor stall during ACC Speed loss occurs to the inverter during ACC Check if the ACC time is too short If it is the inverter fault or interference please contact with our company Overcurrent...

Page 202: ...V F control Adjust the ACC DEC time Check if there is interference source Parameters autotune Check if the ACC DEC time is too short Set right motor type and parameters Check if it needs parameters a...

Page 203: ...and instrument test Conforming to the manual Ensure there are no tools or other foreign or dangerous objects Visual examination There are no tools or dangerous objects Voltage Ensure the main circuit...

Page 204: ...ng expansion Visual examination NA Ensure the safety valve is in the right place Estimate the life time according to the maintenance or measure the electrostatic capacity NA If necessary measure the e...

Page 205: ...to the maintenance information NA Cooling system Cooling fan Estimate whether there is abnormal noise and vibration Hearing and Visual examination or rotate with hand Stable rotation Estimate there i...

Page 206: ...mage to the equipment 1 Stop the inverter and disconnect it from the AC power source and wait for at least the time designated on the inverter 2 Pry the fan from the cabinet with screwdriver and lift...

Page 207: ...voltage for 2 hours Use voltage adjusting power supply to charge the inverter The right selection of the voltage adjusting power supply depends on the supply power of the inverter The single phase 22...

Page 208: ...ectrolytic capacitors if the working hours of electrolytic capacitors in the inverter are above 35000 Please contact with the local offices or dial our national service hotline 400 700 9997 for detail...

Page 209: ...modes for Modbus protocol ASCII mode and RTU Remote Terminal Units mode On one Modbus network all devices should select the same transmission mode and their basic parameters such as baud rate digital...

Page 210: ...sistor 10 3 1 1 Single application Figure 1 is the site Modbus connection figure of single inverter and PC Generally the computer does not have RS485 interface the RS232 or USB interface of the comput...

Page 211: ...on the chrysanthemum connection and star connection are commonly used Chrysanthemum chain connection is required in the RS485 industrial fieldbus standards The two ends are connected to terminal resis...

Page 212: ...uch as baud rate and digital check bit in RS485 should be the same and there should be no repeated address 10 3 2 RTU mode 10 3 2 1 RTU communication frame format If the controller is set to communica...

Page 213: ...CRC checkout the byte of each field is hex 0 9 A F The network device is always monitoring the action of communication bus When the first field the address message is received each device will confirm...

Page 214: ...te The user can select different bit checkouts or non checkout which impacts the check bit setting of each byte The definition of even checkout add an even check bit before the data transmission to il...

Page 215: ...will xor with the preset value If LSB is 0 the action will not carry on Repeat 8 times during the whole process After the last bit is completed the next 8 bit character will xor with the current value...

Page 216: ...4H from the inverter with the address of 01H read the content of data address of 0004H and 0005H the frame structure is as below RTU master command message from the master to the inverter START T1 T2...

Page 217: ...ter to the master for the response of reading command and CMD occupies one byte Byte number means all byte number from the byte excluding the byte to CRC byte excluding the byte 04 means there are 4 b...

Page 218: ...5 bytes ADDR 02H CMD 06H High bit of writing data address 00H Low bit of writing data address 04H High bit of data content 13H Low bit of data content 88H CRC low bit C5H CRC high bit 6EH END T1 T2 T...

Page 219: ...n this part is to control the running of the inverter and get the state information and relative function parameters of the inverter 10 4 4 1 The rules of parameter address of the function codes The p...

Page 220: ...invalid address 10 4 4 2 The address instruction of other function in Modbus The master can operate the parameters of the inverter as well as control the inverter such as running or stopping and monit...

Page 221: ...ar 0 no power consumption clear Bit4 1 pre exciting enabling 0 pre exciting disabling Bit5 1 DC braking enabling 0 DC braking disabling W R 200AH Virtual input terminal command range 0x000 0x1FF W R 2...

Page 222: ...communication addresses of CHF100A and CHV100 R Set frequency 3001H 0 Fmax unit 0 01Hz R Bus voltage 3002H 0 0 2000 0V unit 0 1V R Output voltage 3003H 0 1200V unit 1V R Output current 3004H 0 0 3000...

Page 223: ...only write other than read Note when operating the inverter with the table above it is necessary to enable some parameters For example the operation of running and stopping it is necessary to set P00...

Page 224: ...5 0 50 10 If Modbus communication is used to control the hibernation restore delay time as 5 0s Firstly 5 0 can be magnified by 10 times to integer 50 32H and then this data can be sent After the inv...

Page 225: ...by P7 00 06H Data frame error In the frame message sent by the upper computer the length of the digital frame is incorrect or the counting of CRC check bit in RTU is different from the lower computer...

Page 226: ...f running command channel is 0 2 if it is set to 3 because the number is beyond the range the inverter will return fault response message as below Abnormal response code 86H means the abnormal respons...

Page 227: ...ta all fault types are 0023H decimal 35 with the meaning of maladjustment STo 10 4 7 2 Example of writing command 06H Example 1 Make the inverter with the address of 03H to run forward See table 1 the...

Page 228: ...ftware is the interface commissioning assistant which can be downloaded on the internet The software with CRC checkout function is the best selection At first select COM1 for the serial interface keep...

Page 229: ...bnormal fault The possible reasons for no response to the communication Select wrong serial interface for example if the converter is COM1 select COM2 during the communication The baud rate digital bi...

Page 230: ...ower is limited to 1 5 PN If the limit is exceeded motor torque and current are automatically restricted The function protects the input bridge of the drive against overload 2 The ratings apply at amb...

Page 231: ...r is based on the factory carrier frequency so if it is above the factory value the inverter needs to derate 10 for every additional 1kHz carrier frequency A 3 Grid specifications Grid voltage AC 3PH...

Page 232: ...nt category C2 please refer to EMC regulations A 5 Applicable standards The inverter complies with the following standards EN ISO 13849 1 2008 Safety of machinery Safety related parts of control syste...

Page 233: ...nt Note IEC EN 61800 3 in EMC standard does not limit the power distribution of the inverter but it defines the usage installation and commissioning The professional electrician needs the skills in in...

Page 234: ...l 2 The motor and control cables are selected as specified in this manual 3 The inverter is installed according to the instructions given in this manual 4 For the maximum motor cable length with 4kHz...

Page 235: ...hosit Dimension drawings 234 Dimension drawings Appendix B B 1 What this chapter contains Dimension drawings of the Goodrive300 19 are shown below The dimensions are given in millimeters B 2 Keypad s...

Page 236: ...eries open loop vector inverter special for hosit Dimension drawings 235 B 3 Inverter structure B 4 Dimensions of AC 3PH 380V 15 440V 10 inverters B 4 1 Wall installation Wall installation of 380V 1 5...

Page 237: ...0V 220 315kW inverters Installation dimension of 380V unit mm Model W1 W2 H1 H2 D1 Hole size 1 5kW 2 2kW 126 115 193 175 174 5 5 4kW 5 5kW 146 131 263 243 5 181 6 7 5kW 11kW 170 151 331 5 303 5 216 6...

Page 238: ...0V unit mm Model W1 W2 W3 W4 H1 H2 H3 H4 D1 D2 Hole size 1 5kW 2 2kW 150 115 130 7 5 234 220 190 16 5 174 5 65 5 5 4kW 5 5kW 170 131 150 9 5 292 276 260 10 181 79 5 6 7 5kW 11kW 191 151 174 11 5 370 3...

Page 239: ...loop vector inverter special for hosit Dimension drawings 238 B 4 3 Floor installation Floor installation of 380V 220 315kW inverters Model W1 W2 W3 W4 H1 H2 D1 D2 Hole size 220kW 315kW 750 230 714 6...

Page 240: ...w to select the options and parts of Goodrive300 19 series C 2 Peripherial wiring Below is the peripherial wiring of Goodrive300 19 series inverters Note 1 The inverters 55kW are embedded with braking...

Page 241: ...ters 75kW have external DC reactors DC reactor Input filter Control the electromagnetic interference generated from the inverter please install close to the input terminal side of the inverter or Brak...

Page 242: ...ut cables but a shielded symmetrical cable is recommended Compared to a 4 core conductor system the use of a symmetrical shielded cable reduces electromagnetic emission of the whole drive system as we...

Page 243: ...Run analog and digital signals in separate cables Do not make any voltage tolerance or insulation resistance tests for example hi pot or megger on any part of the drive as testing can damage the drive...

Page 244: ...60G 4 240 120 95 300 95 300 70 300 120 240 GD300 19 185G 4 95 2P 95 95 150 70 150 70 150 35 95 GD300 19 200G 4 95 2P 95 95 150 70 150 70 150 35 95 GD300 19 220G 4 150 2P 150 95 150 70 150 70 150 50 15...

Page 245: ...nside the motor casing will reduce the insulation resistance If moisture is suspected dry the motor and repeat the measurement C 5 Breaker and electromagnetic contactor It is necessary to add fuse for...

Page 246: ...19 110G 4 630 400 315 GD300 19 132G 4 720 400 380 GD300 19 160G 4 870 630 450 GD300 19 185G 4 1110 630 580 GD300 19 200G 4 1110 630 580 GD300 19 220G 4 1230 800 630 GD300 19 250G 4 1380 800 700 GD300...

Page 247: ...aused by supply net voltage transients and harmonic waves of the loads C 6 1 AC 3PH 380V 15 440V 10 Inverter model Input reactor DC reactor Output reactor GD300 19 1R5G 4 ACL2 1R5 4 OCL2 1R5 4 GD300 1...

Page 248: ...2 315 4 Note 1 The rated derate voltage of the input reactor is 2 15 2 The power factor of the input side is above 90 after installing DC reactor 3 The rated derate voltage of the output reactor is 1...

Page 249: ...envirtonment IEC61800 3 2004 category C2 EN 61800 3 2004 C the second envirtonment IEC61800 3 2004 category C3 EN 61800 3 2004 C 7 2 AC 3PH 380V 15 440V 10 Inverter model Input filter Output filter GD...

Page 250: ...energy of the motor and load return to the inverter to charge the capacitors in the main DC circuit When the voltage increases to the limit damage may occur to the inverter It is necessary to apply br...

Page 251: ...19 004G 4 122 0 6 3 4 8 80 GD300 19 5R5G 4 89 0 75 4 1 6 6 60 GD300 19 7R5G 4 65 1 1 5 6 9 47 GD300 19 011G 4 44 1 7 8 3 13 2 31 GD300 19 015G 4 32 2 11 18 23 GD300 19 018G 4 27 3 14 22 19 GD300 19 0...

Page 252: ...he power of the braking resistor properly in the frequent braking situation the frequency usage ratio is more than 10 C 8 2 Select the braking resistor cables Use a shielded cable to the resistor cabl...

Page 253: ...0 19 series open loop vector inverter special for hosit Peripherial options and parts 252 length among BR1 and BR2 and the braking resistor terminals should be no more than 10m Single installation is...

Page 254: ...d serial number of the unit in question A listing of INVT sales support and service contacts can be found on www invt com cn D 1 2 Feedback on INVT inverter manuals Your comments on our manuals are we...

Page 255: ...201610 V2 0 66001 00230 I I...

Reviews: