Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-92-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
DEC time
Setting range: 0.0~3600.0s
on
model
P08.09
Jumping
frequency 1
When the set frequency is in the range of jumping
frequency, the inverter will run at the edge of the
jumping frequency.
The inverter can avoid the mechanical resonance
point by setting the jumping frequency. The inverter
can set three jumping frequency. But this function will
be invalid if all jumping points are 0.
Setting range: 0.00Hz~P00.03 (the Max. frequency)
0.00Hz
○
P08.10
Jumping
frequency
range 1
0.00Hz
○
P08.11
Jumping
frequency 2
0.00Hz
○
P08.12
Jumping
frequency
range 2
0.00Hz
○
P08.13
Jumping
frequency 3
0.00Hz
○
P08.14
Jumping
frequency
range 3
0.00Hz
○
P08.27
Set running
time
Pre-set running time of the inverter. When the
accumulative running time achieves the set time, the
multi-function digital output terminals will output the
signal of
“running time arrival”.
Setting range: 0~65535min
0min
○
P08.28
Fault reset
times
Fault reset times: set the automatic fault reset times.
If the reset time exceeds this set value, the inverter
will stop to wait maintenance.
Interval time of automatic fault reset: the interval
between the time when the fault occurs and the time
when the reset action occurs.
Setting range of P08.28: 0~10
Setting range of P08.29: 0.1~3600.0s
0
○
P08.29
Interval time
of automatic
fault reset
1.0s
○
P08.30
Frequency
decreasing
The output frequency of the inverter changes as the
load. And it is mainly used to balance the power when
0.00Hz
○