Goodrive300-19 series open loop vector inverter special for hosit Technical data
-230-
A.2.2.2 Altitude derating
The device can output rated power if the installation site below 1000m. The output power decreases if
the altitude exceeds 1000 meters. Below is the detailed decreasing range of the derating:
For 3-phase 200V inverter, the maximum altitude is 3000m above sea level. In altitudes
2000…3000m, the derating is 2% for every 100m.
A.2.2.3 Carrier frequency derating
For Goodrive300-19 series inverters, different power level corresponds to different carrier frequency
range. The rated power of the inverter is based on the factory carrier frequency, so if it is above the
factory value, the inverter needs to derate 10% for every additional 1kHz carrier frequency.
A.3 Grid specifications
Grid voltage
AC 3PH 380V (-15%)~440V (+10%)
Short-circuit capacity
Maximum allowed prospective short-circuit current at the input power
connection as defined in IEC 60439-1 is 100kA. The drive is suitable
for use in a circuit capable of delivering not more than 100kA at the
drive maximum rated voltage.
Frequency
50/60Hz ± 5%, maximum rate of change 20%/s
A.4 Motor connection data
Motor type
Asynchronous induction motor
Voltage
0 to U1 (motor rated voltage), 3-phase symmetrical, Umax (inverter
rated voltage) at the field weakening point
Short-circuit
protection
The motor output is short-circuit proof by IEC 61800-5-1
Frequency
0~400Hz