Goodrive300-19 series open loop vector inverter special for hosit Basic operation instruction
-163-
Set
value
Function
Instruction
signals (except for the stopping command) and keep
the current output frequency.
31~32
Reserved
32
Length reset
Length counter clear
33
Frequency setting clear
When the terminal closes, the frequency set by
UP/DOWN can be cleared. All set frequency will be
restored into the reference frequency by the
frequency command channel and the frequency will
come back to the value after the frequency increasing
or decreasing.
34
DC braking
The inverter will begin DC braking after the valid
command.
35
Shift motor 1 to motor 2
Motor-shifting can be controlled after the terminal is
valid.
36
Shift the command to the
keypad
After the function terminal becomes valid, the running
command channel will be shifted into keypad running
command channel and the running command channel
will come back to the original state if the function
terminal is invalid.
37
Shift the command to the
terminal
After the function terminal becomes valid, the running
command channel will be shifted into terminal running
command channel and the running command channel
will come back to the original state if the function
terminal is invalid.
38
Shift the command to the
communication
After the function terminal becomes valid, the running
command channel will be shifted into communication
running command channel and the running command
channel will come back to the original state if the
function terminal is invalid.
39
Pre-magnetized command
Perform pre-exciting if the terminal is valid until the
terminal is invalid.
40~56
Power consumption retention
If the command is valid, the current running of the
inverter will not affect its power consumption.