CHF100A series high performance universal inverter
.34.
1: Terminal (LED flickering)
The operation, including forward run, reverse run, forward jog, reverse jog etc. can be
controlled by multifunctional input terminals.
2: Communication (LED lights on)
The operation of inverter can be controlled by host through communication.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P0.02
UP/DOWN
setting
0: Valid, save UP/DOWN value
when power off
1:
Valid,
do
not
save
UP/DOWN value when power
off
2: Invalid
3: Valid during running, clear
when stop.
0~3
0
0: User can adjust the reference frequency by UP/DOWN. The value of UP/DOWN can
be saved when power off.
1: User can adjust the reference frequency by UP/DOWN, but the value of UP/DOWN
will not be saved when power off.
2: User can not adjust the reference frequency by UP/DOWN. The value of UP/DOWN
will be cleared.
3: User can only adjust the reference frequency by UP/DOWN during the inverter is
running. The value of UP/DOWN will be cleared when the inverter stops.
Notice:
l
UP/DOWN function can be achieved by keypad (
∧
and
∨
) and
multifunctional terminals.
l
Reference frequency can be adjusted by UP/DOWN.
l
UP/DOWN has highest priority which means UP/DOWN is always active no
matter which frequency command source is.
l
When the factory setting is restored (P0.17 is set to be 1), the value of
UP/DOWN will be cleared.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P0.03
Maximum
frequency
10.00~400.00Hz
10.00~400.00
50.00Hz
Summary of Contents for CHF100A-004G-2
Page 1: ......
Page 4: ......
Page 10: ......
Page 11: ......
Page 13: ......
Page 14: ......
Page 59: ......
Page 60: ......
Page 98: ......
Page 100: ......
Page 103: ......
Page 121: ...CHF100A series high performance universal inverter 120 Figure A 16 Open inverter cabinet ...
Page 155: ......
Page 156: ......