CHF100A series high performance universal inverter
.151.
Function
Code
Name
Description
Factory
Setting
Modify
Seri
al
No.
PB.11
Selection of
overtorque (OL3)
0
:
No detection
1
:
Valid detection of
overtorque during running,
then continue running
2
:
Valid detection of
overtorque during running,
then waring and stop
3
:
Valid detection of
overtorque
during
constant speed running,
then continue running
4
:
Valid detection of
overtorque
during
constant speed running,
then waring and stop.
1
232
PB.12
Detection level of
overtorque
1.0%~200.0%
Depends
on model
233
PB.13
Detection time cof
overtorque
0.0~60.0s
0.1s
234
PC Group: Serial Communication
PC.00
Local address
0~247, 0 stands for the
broadcast address
1
O
235
PC.01
Baud rate
selection
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
4
O
236
PC.02
Data format
0: RTU, 1 start bit, 8 data
bits, no parity check, 1
stop bit.
1: RTU, 1 start bit, 8 data
1
O
237
Summary of Contents for CHF100A-004G-2
Page 1: ......
Page 4: ......
Page 10: ......
Page 11: ......
Page 13: ......
Page 14: ......
Page 59: ......
Page 60: ......
Page 98: ......
Page 100: ......
Page 103: ......
Page 121: ...CHF100A series high performance universal inverter 120 Figure A 16 Open inverter cabinet ...
Page 155: ......
Page 156: ......