CHF100A series high performance universal inverter
.75.
The count pulse input channel can be S1~S4 (
≤
200Hz) and HDI.
If function of output terminal is set as preset count reached, when the count value
reaches preset count value (P8.18), it will output an ON-OFF signal. Inverter will clear
the counter and restart counting.
If function of output terminal is set as specified count reached, when the count value
reaches specified count value (P8.19), it will output an ON-OFF signal until the count
value reaches preset count value (P8.18). Inverter will clear the counter and restart
counting.
Notice:
l
Specified count value (P8.19) should not be greater than preset count value
(P8.18).
l
Output terminal can be RO1, RO2.
This function is shown as following figure.
Figure 6.29 Timing chart for preset and specified count reached.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P8.20
Preset
running time
0~65535h
0~65535
65535 h
If function of output terminal is set as running time reached, when the accumulated
running time reaches the preset running time, it will output an ON-OFF signal.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P8.21
FDT level
0.00~ P0.03
0.00~ P0.03
50.00Hz
P8.22
FDT lag
0.0~100.0%
0.0~100.0
5.0%
When the output frequency reaches a certain preset frequency (FDT level), output
terminal will output an ON-OFF signal until output frequency drops below a certain
Summary of Contents for CHF100A-004G-2
Page 1: ......
Page 4: ......
Page 10: ......
Page 11: ......
Page 13: ......
Page 14: ......
Page 59: ......
Page 60: ......
Page 98: ......
Page 100: ......
Page 103: ......
Page 121: ...CHF100A series high performance universal inverter 120 Figure A 16 Open inverter cabinet ...
Page 155: ......
Page 156: ......