CHF100A series high performance universal inverter
.72.
6.9 P8 Group--Enhanced Function
Function
Code
Name
Description
Setting
Range
Factory
Setting
P8.00
Acceleration
time 1
0.1~3600.0s
0.1~3600.0
Depend
on model
P8.01
Deceleration
time 1
0.1~3600.0s
0.1~3600.0
Depend
on model
P8.02
Acceleration
time 2
0.1~3600.0s
0.1~3600.0
Depend
on model
P8.03
Deceleration
time 2
0.1~3600.0s
0.1~3600.0
Depend
on model
P8.04
Acceleration
time 3
0.1~3600.0s
0.1~3600.0
Depend
on model
P8.05
Deceleration
time 3
0.1~3600.0s
0.1~3600.0
Depend
on model
For details, please refer to description of P0.11 and P0.12.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P8.06
Jog reference
0.00~P0.03
0.00~P0.03
5.00hz
P8.07
Jog
acceletation
time
0.1-3600.0s
0.1~3600.0
Depand
on Model
P8.08
Jog
deceleration
time
0.1~3600.0s
0.1~3600.0
Depand
on Model
P8.09
Skip
Frequency 1
0.00~P0.03
0.00~P0.03
0.00hz
P8.10
Skip
Frequency 2
0.00~P0.03
0.00~P0.03
0.00hz
P8.11
Skip
frequency
bandwidth
0.00~P0.03
0.00~P0.03
0.00hz
By means of setting skip frequency, the inverter can keep away from the mechanical
resonance with the load. P8.09 and P8.10 are centre value of frequency to be skipped.
Summary of Contents for CHF100A-004G-2
Page 1: ......
Page 4: ......
Page 10: ......
Page 11: ......
Page 13: ......
Page 14: ......
Page 59: ......
Page 60: ......
Page 98: ......
Page 100: ......
Page 103: ......
Page 121: ...CHF100A series high performance universal inverter 120 Figure A 16 Open inverter cabinet ...
Page 155: ......
Page 156: ......