CHF100A series high performance universal inverter
.42.
l
The starting frequency could be less than the lower frequency limit (P0.05).
l
P1.01 and P1.02 take no effect during FWD/REV switching.
Figure 6.3 Starting diagram.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P1.03
DC Braking
current
before start
0.0~150.0%
0.0~150.0
0.0%
P1.04
DC Braking
time before
start
0.0~50.0s
0.0~50.0
0.0s
When inverter starts, it performs DC braking according to P1.03 firstly, then start to
accelerate after P1.04.
Notice:
l
DC braking will take effect only when P1.00 is set to be 1.
l
DC braking is invalid when P1.04 is set to be 0.
l
The value of P1.03 is the percentage of rated current of inverter. The bigger
the DC braking current, the greater the braking torque.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P1.05
Acceleration /
Deceleration
mode
0: Linear
1: reserved
0~1
0
0: Linear: Output frequency will increase or decrease with fixed acceleration or
deceleration time.
1: Reserved
Notice: CHF100A inverter offers 4 groups of specific acceleration and deceleration