CHF100A series high performance universal inverter
.92.
change; therefore, it is recommended not to enable the function when
inverter needs to output stable frequency
l
During auto current limiting process, if PB.08 is too low, the overload
capacity will be impacted.
Please refer to following figure.
Figure 6.33 Current limiting protection function.
Function
Code
Name
Description
Setting
Range
Factory
Setting
PB.11
Selection of
overtorque
(OL3)
0
:
No detection
1
:
Valid
detection
of
overtorque during running,
then continue running
2
:
Valid
detection
of
overtorque during running,
then warning and stop
3
:
Valid
detection
of
overtorque during constant
speed running, then continue
running 4
:
Valid detection of
overtorque during constant
speed running, then warning
and stop.
0~4
1
PB.12
Detection
level of
overtorque
10.0%~200.0%
10.0~200.0
G
model:
150%
P
model:
120%
Summary of Contents for CHF100A-004G-2