CHF100A series high performance universal inverter
.93.
This value is depending on model.
Function
Code
Name
Description
Setting
Range
Factory
Setting
PB.13
Detection time
cof overtorque
0.0~60.0s
0~60
0.1s
Figure 6.34 Overtorque control function.
If PB.11 is set to be 1or 3, and if the output torque of inverter reaches to PB.12, and with
delay of PB.13, this will output the overtorque. And the TRIP light will reflash. If P6.01
~P6.03 are set to be10, the output will be valid.
If PB.11 is set to be 2 or 4, when overtorque signal meets the output conditions, inverter
proforms warming signal OL3,and meanwhile stops the output.
6.13 PC Group--Serial Communication
Function
Code
Name
Description
Setting
Range
Factory
Setting
PC.00
Local address 0~247
0~247
1
This parameter determines the slave address used for communication with master. The
value
“
0
”
is the broadcast address.
Function
Code
Name
Description
Setting
Range
Factory
Setting
PC.01
Baud rate
selection
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
0~5
4
This parameter can set the data transmission rate during serial communication.
Notice: The baud rate of master and slave must be the same.
Summary of Contents for CHF100A-004G-2
Page 1: ......
Page 4: ......
Page 10: ......
Page 11: ......
Page 13: ......
Page 14: ......
Page 59: ......
Page 60: ......
Page 98: ......
Page 100: ......
Page 103: ......
Page 121: ...CHF100A series high performance universal inverter 120 Figure A 16 Open inverter cabinet ...
Page 155: ......
Page 156: ......