CHF100A series high performance universal inverter
.41.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P0.17
Restore
parameters
0: No action
1: Restore factory setting
2: Clear fault records
0~2
0
0: No action
1: Inverter restores all parameters to factory setting except P2 group.
2: Inverter clear all fault records.
This function code will restore to 0 automatically when complete the function operation.
6.2 P1 Group --Start and Stop Control
Function
Code
Name
Description
Setting
Range
Factory
Setting
P1.00
Start Mode
0: Start directly
1: DC braking and start
2: Speed tracking and start
0~2
0
0: Start directly: Start the motor at the starting frequency determined by P1.01.
1: DC braking and start: Inverter will output DC current firstly and then start the motor at
the starting frequency. Please refer to description of P1.03 and P1.04. It is suitable for
the motor which have small inertia load and may reverse rotation when start.
2: Speed tracking and start: Inverter detects the rotation speed and direction of motor,
then start running to its reference frequency based on current speed. This can realize
smooth start of rotating motor with big inertia load when instantaneous power off.
Notice: It only applies on the inverter of 7.5kW and above.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P1.01
Starting
frequency
0.00~10.00Hz
0.00~10.00
0.00Hz
P1.02
Hold time of
starting
frequency
0.0~50.0s
0.0~50.0
0.0s
Notice:
l
Set proper starting frequency can increase the starting torque.
l
If the reference frequency is less than starting frequency, inverter will be at
stand-by status. The indicator of RUN/TUNE lights on, inverter has no output.
Summary of Contents for CHF100A-004G-2
Page 1: ......
Page 4: ......
Page 10: ......
Page 11: ......
Page 13: ......
Page 14: ......
Page 59: ......
Page 60: ......
Page 98: ......
Page 100: ......
Page 103: ......
Page 121: ...CHF100A series high performance universal inverter 120 Figure A 16 Open inverter cabinet ...
Page 155: ......
Page 156: ......