CHF100A series high performance universal inverter
.104.
voltage to rated input voltage gradually. The drive should be powered for 5 hours without
load.
8.2.7 Before performing insulation tests, all main circuit input/output terminals should
be short-circuited with conductors. Then proceed insulation test to the ground. Insulation
test of single main circuit terminal to ground is forbidden; otherwise the drive might be
damaged. Please use a 500V Mega-Ohm-Meter.
8.2.8 Before the insulation test of the motor, disconnect the motor from the drive to
avoid damaging it.
8.3 Replacement of wearing parts
Fans and electrolytic capacitors are wearing part, please make periodic replacement to
ensure long term, safety and failure-free operation. The replacement periods are as
follows:
◆
Fan: Must be replaced when using up to 20,000 hours;
◆
Electrolytic Capacitor: Must be replaced when using up to 30,000~40, 000 hours.