CHF100A series high performance universal inverter
.69.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P7.08
Stop status
display
selection
0~0xFFFF
0~0xFFFF
0x00FF
P7.08 determines the display parameters in stop status. The setting method is similar
with P7.06.
The display content corresponding to each bit of P7.08 is described in the following
table:
BIT7
BIT6
BIT5
BIT4
BIT3
BIT2
BIT1
BIT0
AI2
AI1
PID
feedback
PID
preset
Output
terminal
status
Input
terminal
status
DC bus
voltage
Reference
frequency
BIT15
BIT14
BIT13
BIT12
BIT11
BIT10
BIT9
BIT8
Reserved Reserved Reserved Reserved Reserved
Torque
setting
value
Step No. of
PLC or
multi-step
HDI
frequency
Function
Code
Name
Description
Setting
Range
Factory
Setting
P7.09
Coefficient of
rotation speed
0.1~999.9%
0.1~999.9
100.0%
This parameter is used to calibrate the bias between actual mechanical speed and
rotation speed. The formula is as below:
Actual mechanical speed = 120 * output frequency *P7.09 / Number of poles of motor.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P7.10
Coefficient of
line speed
0.1~999.9%
0.1~999.9
1.0%
This parameter is used to calculate the line speed based on actual mechanical speed.
The formula is as below:
Line speed = actual mechanical speed * P7.10
Summary of Contents for CHF100A-004G-2
Page 1: ......
Page 4: ......
Page 10: ......
Page 11: ......
Page 13: ......
Page 14: ......
Page 59: ......
Page 60: ......
Page 98: ......
Page 100: ......
Page 103: ......
Page 121: ...CHF100A series high performance universal inverter 120 Figure A 16 Open inverter cabinet ...
Page 155: ......
Page 156: ......