CHF100A series high performance universal inverter
.109.
same reason. The description below is data format in RTU mode.
Protocol data unit format of reading parameters:
Request format:
Protocol data unit
Data length(bytes)
Range
Command
1
0x03
Data Address
2
0~0xFFFF
Read number
2
0x0001~0x0010
Reply format (success):
Protocol data unit
Data length(bytes)
Range
Command
1
0x03
Returned byte number
2
2* Read number
Content
2* Read number
If the command is reading the type of inverter (data address 0x3016), the content value
in reply message is the device code:
The high 8 bit of device code is the type of the inverter, and the low 8 bit of device code
is the sub type of inverter.
For details, please refer to the following table:
High byte
Meaning
Low byte
Meaning
01
Vector control type
02
For water supply
03
Middle frequency 1500Hz
00
CHV
04
Middle frequency 3000Hz
01
Vector control type
01
CHE
02
Middle frequency 1500Hz
01
Universal type
02
CHF
02
Vector type CHF100A
If the operation fails, the inverter will reply a message formed by failure command and
error code. The failure command is (Command
+
0x80). The error code indicates the
reason of the error; see the table below.
Value
Name
Mean
01H
Illegal
command
The command from master can not be executed. The
reason maybe:
1 This command is only for new version and this version can
not realize.
Summary of Contents for CHF100A-004G-2
Page 1: ......
Page 4: ......
Page 10: ......
Page 11: ......
Page 13: ......
Page 14: ......
Page 59: ......
Page 60: ......
Page 98: ......
Page 100: ......
Page 103: ......
Page 121: ...CHF100A series high performance universal inverter 120 Figure A 16 Open inverter cabinet ...
Page 155: ......
Page 156: ......