CHF100A series high performance universal inverter
.137.
Function
Code
Name
Description
Factory
Setting
Modify
Seri
al
No.
3: 3-wire control mode 2
P5.11
UP/DOWN setting
change rate
0.01~50.00Hz/s
0.50Hz/s
O
83
P5.12
AI1 lower limit
-10.00V~10.00V
0.00V
O
84
P5.13
AI1 lower limit
corresponding
setting
-100.0%~100.0%
0.0%
O
85
P5.14
AI1 upper limit
-10.00V~10.00V
10.00V
O
86
P5.15
AI1 upper limit
corresponding
setting
-100.0%~100.0%
100.0%
O
87
P5.16
AI1 filter time
constant
0.00s~10.00s
0.10s
O
88
P5.17
AI2 lower limit
0.00V~10.00V
0.00V
O
89
P5.18
AI2 lower limit
corresponding
setting
-100.0%~100.0%
0.0%
O
90
P5.19
AI2 upper limit
0.00V~10.00V
10.00V
O
91
P5.20
AI2 upper limit
corresponding
setting
-100.0%~100.0%
100.0%
O
92
P5.21
AI2 filter time
constant
0.00s~10.00s
0.10s
O
93
P5.22
HDI lower limit
0.0 kHz ~50.0kHz
0.0KHz
O
94
P5.23
HDI lower limit
corresponding
setting
-100.0%~100.0%
0.0%
O
95
P5.24
HDI upper limit
0.0 KHz~50.0KHz
50.0KHz
O
96
P5.25
HDI upper limit
corresponding
setting
-100.0%~100.0%
100.0%
O
97
Summary of Contents for CHF100A-004G-2
Page 1: ......
Page 4: ......
Page 10: ......
Page 11: ......
Page 13: ......
Page 14: ......
Page 59: ......
Page 60: ......
Page 98: ......
Page 100: ......
Page 103: ......
Page 121: ...CHF100A series high performance universal inverter 120 Figure A 16 Open inverter cabinet ...
Page 155: ......
Page 156: ......