CHF100A series high performance universal inverter
.95.
Function
Code
Name
Description
Setting
Range
Factory
Setting
according to P1.06 (if
P0.01=2)
3: No alarm but stop
according to P1.06
0: When communication error occurs, inverter will alarm (CE) and coast to stop.
1: When communication error occurs, inverter will omit the error and continue to run.
2: When communication error occurs, if P0.01=2, inverter will not alarm but stop
according to stop mode determined by P1.06. Otherwise it will omit the error.
3: When communication error occurs, inverter will not alarm but stop according to stop
mode determined by P1.06.
Function
Code
Name
Description
Setting
Range
Factory
Setting
PC.06
Response
action
Unit
’
s place of LED
0: Response to writing
1: No response to writing
Ten
’
s place of LED
0: Reference not saved when
power off
1: Reference saved when
power off
00~11
00
Figure 6.35 Meaning of PC.06.
A stands for: Unit
’
s place of LED.
B stands for: Ten
’
s place of LED