CHF100A series high performance universal inverter
.131.
Function
Code
Name
Description
Factory
Setting
Modify
Seri
al
No.
P1.04
DC Braking time
before start
0.0~50.0s
0.0s
¥
22
P1.05
Acceleration /
Deceleration
mode
0: Linear
1: reserved
0
¥
23
P1.06
Stop mode
0: Deceleration to stop
1: Coast to stop
0
O
24
P1.07
Starting frequency
of DC braking
0.00~P0.03
0.00Hz
O
25
P1.08
Waiting time
before
DC braking
0.0~50.0s
0.0s
O
26
P1.09
DC braking
current
0.0~150.0%
0.0%
O
27
P1.10
DC braking time
0.0~50.0s
0.0s
O
28
P1.11
Dead time of
FWD/REV
0.0~3600.0s
0.0s
O
29
P1.12
Action when
running frequency
is less than lower
frequency limit
0: Running at the lower
frequency limit
1: Stop
2: Stand-by
0
¥
30
P1.13
Delay time for
restart
0.0~3600.0s
0.0s
O
31
P1.14
Restart after
power off
0: Disabled
1: Enabled
0
O
32
P1.15
Waiting time of
restart
0.0~3600.0s
0
O
33
P1.16
Terminal function
examined when
power is on
0: Disabled
1: Enabled
0
¥
33