CHF100A series high performance universal inverter
.83.
0: Stop after one cycle: Inverter stops automatically as soon as it completes one cycle,
and It needs run command to start again.
1: Hold last frequency after one cycle: Inverter holds frequency and direction of last step
after one cycle.
2: Circular run: Inverter continues to run cycle by cycle until receive a stop command.
Figure 6.28 Simple PLC operation diagram.
Function
Code
Name
Description
Setting
Range
Factory
Setting
PA.01
Simple PLC
status saving
after power off
0: Disabled
1: Enabled
0~1
0
This parameter determines whether the running step and output frequency should be
saved when power off or not.
Function
Code
Name
Description
Setting
Range
Factory
Setting
PA.02
Multi-step
speed 0
-100.0~100.0%
-100.0~100.0
0.0%
PA.03
0
th
Step
running time
0.0~6553.5 s(m)
0.0~6553.5
0.0s
PA.04
Multi-step
speed 1
-100.0~100.0%
-100.0~100.0
0.0%
PA.05
1
st
Step
running time
0.0~6553.5 s(m)
0.0~6553.5
0.0s
PA.06
Multi-step
speed 2
-100.0~100.0%
-100.0~100.0
0.0%