CHF100A series high performance universal inverter
.147.
Function
Code
Name
Description
Factory
Setting
Modify
Seri
al
No.
P9.04
Proportional gain
(Kp)
0.00~100.00
0.10
O
176
P9.05
Integral time (Ti)
0.01~10.00s
0.10s
O
177
P9.06
Differential time
(Td)
0.00~10.00s
0.00s
O
178
P9.07
Sampling cycle (T) 0.00~100.00s
0.10s
O
179
P9.08
Bias limit
0.0~100.0%
0.0%
O
180
P9.09
Feedback lost
detecting value
0.0~100.0%
0.0%
O
181
P9.10
Feedback lost
detecting time
0.0~3600.0s
1.0s
O
182
PA Group: Simple PLC and Multi-step Speed Control
PA.00
Simple PLC mode
0: Stop after one cycle
1: Hold last frequency
after one cycle
2: Circular run
0
O
183
PA.01
Simple PLC status
saving after power
off
0: Disabled
1: Enabled
0
O
184
PA.02
Multi-step speed 0 -100.0~100.0%
0.0%
O
185
PA.03
0th Step running
time
0.0~6553.5s(h)
0.0s
O
186
PA.04
Multi-step speed 1 -100.0~100.0%
0.0%
O
187
PA.05
1st Step running
time
0.0~6553.5s(h)
0.0s
O
188
PA.06
Multi-step speed 2 -100.0~100.0%
0.0%
O
189
PA.07
2nd Step running
time
0.0~6553.5s(h)
0.0s
O
190
PA.08
Multi-step speed 3 -100.0~100.0%
0.0%
O
191
PA.09
3rd Step running
time
0.0~6553.5s(h)
0.0s
O
192
Summary of Contents for CHF100A-004G-2
Page 1: ......
Page 4: ......
Page 10: ......
Page 11: ......
Page 13: ......
Page 14: ......
Page 59: ......
Page 60: ......
Page 98: ......
Page 100: ......
Page 103: ......
Page 121: ...CHF100A series high performance universal inverter 120 Figure A 16 Open inverter cabinet ...
Page 155: ......
Page 156: ......