CHF100A series high performance universal inverter
.88.
High byte
BIT 8
BIT 9
BIT 10
BIT 11
BIT 12
BIT 13
BIT 14
BIT 15
PA.34
0
1
1
0
1
1
0
0
PA.35
0
0
0
0
0
1
0
1
So the value of PA.34 should be: 0X36E4, the value of PA.35 should be: 0XA02F
Function
Code
Name
Description
Setting
Range
Factory
Setting
PA.36
Simple PLC
restart
selection
0: Restart from step 0
1: Continue from interrupted
step
0~1
0
0: Restart from step 0: If the inverter stops during running (due to stop command or fault),
it will run from step 0 when it restarts.
1: Continue from interrupted step: If the inverter stops during running (due to stop
command or fault), it will record the running time of current step. When inverter restarts,
it will resume from interrupted time automatically. For details, please refer to following
figure.
Figure 6.30 Simple PLC continues from interrupted step.
Function
Code
Name
Description
Setting
Range
Factory
Setting
PA.37
Time unit
0: Second
1: Minute
0~1
0
This parameter determines the unit of x step running time.
6.12 PB Group-- Protection Function
Function
Code
Name
Description
Setting
Range
Factory
Setting
PB.00
Input
phase-failure
protection
0: Disable
1: Enable
0~1
1
Summary of Contents for CHF100A-004G-2
Page 1: ......
Page 4: ......
Page 10: ......
Page 11: ......
Page 13: ......
Page 14: ......
Page 59: ......
Page 60: ......
Page 98: ......
Page 100: ......
Page 103: ......
Page 121: ...CHF100A series high performance universal inverter 120 Figure A 16 Open inverter cabinet ...
Page 155: ......
Page 156: ......