Lift controller MLC 8000
Operating manual V2.0
20/196
1. Menu level
2. Menu level
3. Menu level
4. Menu level
Description
Wt.CC Main[s]
Time until door closing when the lift has approached a floor due to a
car call (just for main floor; see above)
Wt.LC Main[s]
Time until door closing when the lift has approached a floor due to a
landing call (whether simultaneously a car call existed).
(just for main floor; see above)
Wt.nC Main[s]
If the lift is on a floor and there is no further call, then the lift closes
after this time the doors after that time (unless "Parking with open
door" is set; see Door parameters)
(just for main floor; see above)
Doorstop[s]
Time Door Stop push stays active until pressed
Wt.Start[ms]
Start delay after closing of the safety circuit of the shaft doors
("Debouncing")
Wt.door[s]
Max. w aiting time for safety circuit doors when starting
Errdelay[s]
Waiting time between the occurrence of an error and further reactions
of the lift controller (call canceling, setting the fault relay, sending an
error message via the remote data transmission, etc.)
Drive parameter
General
Drive
Selection of interface between lift controller and drive unit:
- Standard: control of the drive only via relays of the main board
- CAN-Lust: Inverter "Lust" connected by CAN bus
- CAN-ASE: Using an ASE board (UEA) as interface to lift controller
- CAN-Open: Inverter interface according to CANopen Lift (DSP 417)
- Em.RS485: Emerson inverter connected by RS485
Star/D. [ms]
Changeover time star / delta (hydraulic lifts)
Startdel[ms]
Delay between switching on running contactors and setting control
signals (only if parameter "Sign.delayed" (see below) is set to "Yes" at
the same time)
Brakedel[ms]
Delay between setting control signals and switching on brake
contactor
Brakeoff[ms]
Delay between switching off the control signals and brake contactor
Offdel. [ms]
Delay between switching off brake contactor and main / direction
contactor
Stopdel.[ms]
Delay between switching off all contactors and dir enable
signals
Stop [ms]
Waiting time after shutdown of all control signals and contactors until