INTEC GmbH
22/12/2016
Lift controller MLC 8000
Operating manual V2.0
16/196
2. Menu structure
1. Menu level
2. Menu level
3. Menu level
4. Menu level
Description
Parameter
General paramet.
No.
Lift number (for information only)
Lift type
Rope / Hydraulic
Bottom floor
Bottom floor
Top floor
Top floor
Group size
Number of lifts per group (1 … 8)
Group number
Number of lift within a group (1 … 8)
Car door numb.
Car door number (1 … 3)
Main floor
Main floor
Park floor
Park floor
(Note: Starting with version 1.32z this parameter is in a separate
submenu "Special parameter" - "Parking trip")
Type
Collecting control / Single call control
Setup ready
This value is set to "Yes" if setup is completed. As long as this value
is set to "No", all position values are invalid and the lift does not
handle trips (only electrical recall operation and inspection possible)
Push control
If set to "Yes" lift is working as a "Push control", ie, the lift only goes
as long as special pushs are pressed (also called Deadman control).
Note: As of version 1.36m HSE, this parameter is in the submenu
"special parameters" - "Push control "
Call config.
If set to "Yes" special "call tables" (see "Special parameter") are
activated. If the lift arrives a floor by a landing call, only car calls
enabled for this landing call ("Call table" will be handled.
A maximum of 5 different call configurations can be set. Switching
between the Call configurations occurs only when all doors are closed
and (if available), the presence sensor signals "Car empty" signals
that no one is inside the car anymore.
In principle, up to 5 "logical" lifts can be created for one "real" lift , in
which only floors or entrances within this "logic" lift can be
approached.