Operation
96 / 121
8.3
Switch positions
Listed below are the switch positions that can be called up via the segment display and the “
UP
” / “
OK
” keys on the AMB 32.
The switch positions can be used for inputs (
A
/
b
/
C
/
I
/
o
/
T
/
U
/
W
/
X
) or for polling purposes (
E
/
F
/
N
/
T
/
V
).
Stored under the rotary switch procedure is a
time-out
(approx. 5 s). If within this time period a process is not continued or
completed, it is interrupted and the segment display automatically returns to the normal state (flashing point).
Pos. Area / Display
Purpose
Meaning / Procedure
A
A11
Normative system limits compliant with EN 54-20, Class A
b
b11
/
b21
Normative system limits compliant with EN 54-20, Class B
C
C11
/
C21
/
C31
Normative system limits compliant with EN 54-20, Class C
E
E01
to
E99
G00
to
G99
Event memory, 99 events (
E01
= last event)
Event group
G00
to
G99
see Sec. 8.5.3
F
F00
to
F99
(3 x)
Displays the firmware version
see Sec. 7.3.6
I
IA1
IF1
IP1
IE1
Trigger
(
Initiate
);
Test alarm (
IA1
), up to the FACP
Test fault (
IF1
), up to the FACP
Test pre-signal (
IP1
), up to the FACP
Test Alarm 2 (
IE1
), up to the FACP
see Sec. 7.7.2
N
IP
/
Sub
/
GA
169.
/
254.
/
001.
/
001
(default)
Polling IP setting
(
Network
);
IP address (
IP
),
Subnet
(
Sub
),
Gateway
(
GA
)
see Sec. 7.6.1
o
o00
Log off additional modules;
(optional modules, all at same time)
see Sec. 7.3.7
T
Y10
to
Y99
/
M01
to
M12
d01
to
d31
/
H00
to
H23
M00
to
M59
/
S00
to
S59
Polling (
TRE
) and setting (
TSE
) the date and time
see Sec. 7.3.4
U
U01
Executes initial reset
see Sec. 7.3.5
V
V01
,
000
to
255
Volume rate of flow output in %
see Sec. 7.6.1
W
W11
to
W44
Non-normative system limits
X
X01
to
X03
Configurable switch positions
see Sec. 7.2.1
Notice
The table lists only the available switch positions. A detailed description of the operator functions (input pro-
cedure) can be found in the relevant Sec. (“Meaning / Procedure” column).