Commissioning
83 / 121
7.3.2
Commissioning with “ASD Config” configuration software
The workflow for commissioning when using the “
ASD Config
” configuration software is shown below. The “
ASD Config
” con-
figuration software is required only if changes have to be made to the default configuration profile (Sec. 7.2.1) or if the
“ASD
PipeFlow
” calculation software has been used.
Fig. 44 Workflow for commissioning with “ASD Config” configuration software
Point of departure: tube system(s) mounted and connected to
ASD. Smoke sensor(s) deployed in the ASD.
(e.g.
) or
ASD
b21
Switch setting defined acc. to tube system
“
”
specification acc. to “
” know after calculation.
PipeFlow
Switch on supply voltage (FACP). The fan accelerates stepwise
to ist defined speed (takes about 100 s). The next process can
nevertheless be performed immediately.
Change, save and set for operation
in switch position
,
or
.
X01 X02 X03
Change and save on device level (independent
of switch position A, b, C, W or X).
Select required switch position for operation
acc. to Sec. 4.4.4.3 (e.g.
).
b21
“
”
no
no
yes
. 7.3.5
Workflow Sec
. 7.3.3
Workflow Sec
After switching on, a
perform initial reset
minimum waiting time of 2 min
System in operation; commissioning ended
Switch on PC; start ASD
“
”
Config
Settings changes
acc. to
table A and B
(Sec. 7.2.1)
Settings changes
acc. to table C
(Sec. 7.2.1)
Set date and time (apply from PC)
Commissioning workflow
“
”
using ASD
Config
configuration software
System is armed
ASD532