Faults
113 / 121
10.3
Finding and rectifying faults
10.3.1
Fault states
In the event of a fault the fault profile can be localised using the event memory and the corresponding event code display,
which is obtained using the segment display on the AMB 32 (switch position
E
). The following table lists the event codes of
possible fault states and how to rectify them. A list of all the event codes is provided in Sec. 8.5.4.3.
Notice
Multiple codes
: If there are multiple events for any given event group, the display readings are added together.
Example: Display
012
= event code
004
and
008
.
G10, smoke sensor events
Code Meaning:
Check:
Possible causes and remedy:
002
Smoke sensor dust
Check smoke sensor chamber, sampling
pipe and filter-box/filter unit for dust depos-
its
•
Clean interior of smoke sensor cham-
ber and insect protection screen
•
Check and clean sampling pipe and, if
necessary, filter-box/filter unit
•
Replace smoke sensor
004
Smoke sensor dirt
Check smoke sensor chamber, sampling
pipe and filter-box/filter unit for dirt deposits
•
Clean interior of smoke sensor cham-
ber and insect protection screen
•
Check and clean sampling pipe and, if
necessary, filter-box/filter unit
•
Replace smoke sensor
G11, smoke sensor faults, part 1
Code Meaning
Check:
Possible causes and remedy:
001
ASD <> smoke sensor communications
Ribbon cable connection
AMB, smoke sensor
•
Ribbon cable not correctly attached or
defective
check, replace
•
Smoke sensor defective
replace
•
AMB defective
replace
002
Unknown smoke sensor type
(production fault)
Smoke sensor
•
Replace smoke sensor
004
Response sensitivity too low
Correct smoke sensor installed
SSD 532-1, -2, -3
•
Selected response sensitivity is too low
for the deployed smoke sensor type
•
Use different smoke sensor
•
Increase response sensitivity
008
Invalid parameters, smoke sensor
(production fault)
Smoke sensor
•
Replace smoke sensor
G12, smoke sensor faults, part 2
Code Meaning
Check:
Possible causes and remedy:
001
Smoke sensor measuring chamber
Smoke sensor
•
Smoke sensor defective
replace
002
Temperature, smoke sensor
ASD ambient temperature
Smoke sensor
•
Adhere to ambient temperature specifi-
cations
•
Smoke sensor defective
replace
004
Supply voltage, smoke sensor
Check ASD operating voltage
AMB, smoke sensor
•
Set operating voltage correctly
•
AMB defective
replace
•
Smoke sensor defective
replace
008
EEPROM access error, smoke sensor
Smoke sensor
•
Smoke sensor defective
replace
016
EEPROM invalid data, smoke sensor
Smoke sensor
•
Smoke sensor defective
replace
032
Manufacturing, smoke sensor
Smoke sensor
•
Smoke sensor defective
replace
ASD532
Operating
Manual