Commissioning
87 / 121
7.3.7
Logging off additional modules XLM 35, RIM 36, SIM 35 and the SD memory card
The additional modules (XLM 35, SIM 35, RIM 36) or the SD memory card are automatically detected when the device is
switched on; from that point onwards, they are monitored and fully functional. The SD memory card begins with data logging,
recognisable on the flashing Com LED on the AMB. To eject the SD memory card or remove a subsequently fitted additional
module (e.g. because it is not being used), the additional modules and SD memory card must first be logged off via the
AMB 32 main board.
Notice
A time-out (approx. 15 s) is configured for the logoff procedure. During this time the additional modules can be
electrically disconnected from the AMB 32 trouble-free or the SD memory card
can be removed from the ASD. If
no component is removed during that time (including removing the SD memory card), the additional modules are
re-activated and data logging continues.
Measure
Display
Procedure / remarks
(1)
Press key
flashing
C31
or other
•
Displays the default setting or the installation-
specific switch position
(2)
Press the key again until the
display is on
-
o
----
in succession
A
/
b
/
C
/
E
/
F
/
I
/
o
•
Displays the switch position group
o
(3)
Press key
o00
•
Displays logoff additional module
(4)
Press the key again
flashing
o - -
(timeout approx. 15 s)
•
Start logoff procedure, duration approx. 15 s
(5)
Electrically disconnect (ribbon
cable) the relevant additional
module from the AMB 32 within
the logoff time (15 s) or remove
the SD memory card.
•
If the module is not electrically disconnected from
the AMB 32 within 15 s (including removal of the
SD memory card), it is re-activated and data log-
ging continues.
7.4
Re-programming
Warning
The parameters are configured ex factory with default states and values so that the triggering properties comply
with EN 54-20. Changing the parameters may result in non-compliance with EN 54-20. Any adjustments or modi-
fications to the ASD 532 using the “
ASD Config
” configuration software or the user interface on the FACP may
only be carried out by the manufacturer or by qualified personnel trained by the manufacturer.
7.4.1
Re-programming on the ASD 532
If a different switch setting has to be selected within the preset system limits (
A11
to
C31
or
W01
to
W44
), re-programming is
performed as described in Sec. 7.3.3.
7.4.2
Re-programming with “ASD Config” configuration software
When changing parameters as described in Sec. 7.2.1 and 7.2.2, use the “ASD Config” configuration software.
7.4.3
Re-programming from SecuriFire / Integral with XLM 35
When connecting to the SecuriFire or Integral FACP via an XLM 35, control operations and changes can be made to the ASD
device configuration directly from the FACP. For this purpose the FACP user software “SecuriFire Studio” and “
Integral Appli-
cation Center
” are used to start the “ASD Config” configuration software for access to the ASDs; the configuration software is
then used to make changes to the ASD 532.
UP
UP
OK
OK
ASD532
Operating
Manual
Summary of Contents for ASD 532
Page 1: ...ASD 532 Aspirating Smoke Detector Operating Manual ...
Page 2: ...2 88 ASD532 Operating Manual ...
Page 6: ...6 121 ASD532 Operating Manual ...
Page 7: ...Document history 7 121 Document history First edition Date 15 10 2015 ASD532 Operating Manual ...