Commissioning
84 / 121
7.3.3
Setting to pre-defined switch positions A11 to C31, W01 to W44
The following describes the procedure when the ASD 532 has to be set on one of the fixed parameterized switch settings
A11
to
C31
or
W01
to
W44
.
Example:
The ASD 532 is to respond in compliance with EN 54-20, Class B. The sampling pipes are U-shaped, within system
limit 2. As specified in Sec. 4.4.4.3, switch setting
b21
must be selected.
Warning
Switch settings
W01
to
W44
may be used only after consulting with the manufacturer. The airflow monitoring val-
ues stored under those switch positions are
not
tested in accordance with EN.
Measure
Display
Procedure / remarks
(1)
Press key
flashing
C31
•
Displays the default setting
(2)
Press the key again until the
display is on
-
b
----
in succession
A
/
b
•
Displays the switch position group
b
(3)
Press key
b11
•
Displays the smallest possible switch position in
group
b
(4)
Press the key until the display
is on
-
b21
in succession
b11
/
b21
•
Displays the possible switch positions in group
b
(5)
Press key
flashing
b - -
(approx. 4 x)
•
New setting is programmed
(6)
Press the key to check the
change
lasching
b21
•
Displays the new setting
UP
UP
OK
UP
OK
UP
ASD532 Operating Manual