Mounting
54 / 121
5
Mounting
5.1
Mounting guidelines
Notice
Material and products;
only the following materials supplied, approved and listed by the manufacturer may be
used to create the system:
•
Detector housings, smoke sensors, additional modules;
•
Tube materials and fittings for the sampling pipe, accessory materials, pipe clamps (according to T 131 194).
Materials from other sources do not conform to EN 54-20 approval and may only be used if the manufacturer’s
written consent has been obtained.
Installation materials such as cables, intermediate distributors and fastening materials are usually supplied by the
customer.
Tools for handling the detector housing:
The tools listed below are required for mounting and installation
(sorted in the sequence in which they are used in this document):
•
Opening the detector housing
flat-blade screwdriver No. 5 (8 mm)
•
Removing the pipe plug
flat-blade screwdriver No. 2 (4 mm)
•
Securing the detector housing
Torx screwdriver T20
•
Module holder for additional modules
Torx screwdriver T15
•
Terminals
no. 1 flat-blade screwdriver (3.5 mm)
•
Replacing printed AMB circuit boards
Torx screwdriver T10
•
Replacing the aspirating fan unit
Torx screwdriver T15
5.2
Dimensioned drawing / drilling plan for the detector housing
Fig. 14 Detector housing dimensioned drawing and drilling plan
2
9
0
a
p
p
ro
x
.
2
3
13
2
0
74
74
195
20
24
27
140
6
.5
10
154
20.5
20.5
2
4
9
2
0
.5
2
0
.5
ASD532 Operating Manual
Summary of Contents for ASD 532
Page 1: ...ASD 532 Aspirating Smoke Detector Operating Manual ...
Page 2: ...2 88 ASD532 Operating Manual ...
Page 6: ...6 121 ASD532 Operating Manual ...
Page 7: ...Document history 7 121 Document history First edition Date 15 10 2015 ASD532 Operating Manual ...