Operation
99 / 121
8.5.4
Displaying and reading out the event memory
The event memory can be called up via switch position
E
. Up to 99 events can be stored in the event memory (
E01
to
E99
),
with event
E01
as the latest (more recent) event. If the memory exceeds 99 events, the oldest event is deleted. The event
memory as a whole can be deleted only by the manufacturer.
Events are subdivided into groups (
G00
to
G99
) so they can be displayed using the 3 digits of the segment display. For each
event group, up to 8 events can be displayed as a 3-digit code. The codes are added together and displayed if there are multi-
ple pending events per event group.
8.5.4.1
Procedure and interpretation of the event memory display
The sequence below provides an example to illustrate how the next to last event, i.e. the second most recent event, is read out
(
E02
). The result shows that the smoke sensor alarm has triggered.
Measure
Display
Procedure / remarks
(1)
Briefly press the “UP” key on the
AMB 32
flashing, e.g.
b21
or other
•
When commissioning, display of the switch set-
tings
A11
to
C31
,
W01
to
W44
,
X01
to
X03
(2)
Press the “UP” key again (4 x) until
display reads
E
in succession
A
/
b
/
C
/
E
•
Displays the switch position group
E
(3)
Press the “OK” key
E01
•
Selects event
E01
(last, i.e. most recent)
(4)
Press the “UP” key
E02
•
Even selection
E02
(next to last)
(5)
Press the “OK” key
flashing after approx. 2 s, e.g.
G10
•
Displays the event group
G10
, smoke sensor
events
(6)
Wait
flashing after approx. 2 s, e.g.
001
•
Displays event codes
001
, smoke sensor alarm
Notice
Multiple codes
: If pre-signals 1 to 3 preceded the alarm release of smoke sensor, Point
(6)
will display code
057
as the result. It consists of the individual codes (added together)
001
(alarm),
008
(pre-signal 1),
016
(pre-
signal 2) and
032
(pre-signal 3).
Please refer to Sec. 8.5.4.2 and 8.5.4.3 for a list of all the event groups and their events (codes).